Why we connect the capacitor in Delta?if we conect in Star
what will happen?
Answer Posted / faraz ahmed
Wye connected capacitors connected to motors are not
appropriate because they are ungrounded and thus present a
potential difference on each phase of the capacitor which
contributes to the over-all deterioration of the capacitor.
As can be seen in fig.1 below, the failure of any one cell
of a Wye connected capacitor presents an unbalanced load to
the motor. This will effectively destroy the motor due to
unbalanced voltage, temperatures.
Example: If you have a 100HP motor and an unbalance of 5%,
this will cause a power loss of 25%. (100HP – 25% = 75HP).
If the motor was loaded to 85%, the motor now becomes
overloaded. The motor would run 113.5% overloaded, therefore
overheated and will eventually burn out.
Unprotected Wye connected capacitors should not be used for
Power Factor correction. The unbalance protection required
for this type of application is more costly than the
capacitors themselves and therefore not included with Wye
connected capacitors.
Wye connected capacitors do not circulate harmonics and thus
are much more vulnerable to failure due to harmonics.
Fig.1 - The total capacitance for the example above with a
failed cell would be 5kVAR
Delta connected three phase capacitors are more friendly to
the electrical environment. They not only provides
capacitance to each phase but also provides no voltage
unbalances (harmonics).
If a capacitor cell should fail for any reason in one phase,
we are going from a closed delta to an open delta
configuration and in this instance the voltages on each
phase stays the same (see fig.2 below). Failure of a
capacitor cell would only mean a drop in the kVAR on the
circuit. In other words, a 30kVAR delta connected three
phase capacitor with a failed cell would provide 20kVAr to
the electrical system instead of 30kVAR.
Delta connected capacitors unlike the Wye connected
capacitors are able to circulate harmonics currents within
the delta circuit. By doing so it reduces the harmonics on
the electrical system.
Fig.2 - The total capacitance for the example above with a
failed cell would be 20kVAR
| Is This Answer Correct ? | 10 Yes | 0 No |
Post New Answer View All Answers
why effective resistance should be more than static resistance in transmission line?
How to calculate size of HT breaker with the help of Amp (current)? Please provide answers with examples.
what is mean by Digital Logic Meter (DLM)
i have attended the interview on 4th June,08 at Kolkata in IOCL, can anybody tell me what is its result
when measure the core loss of three phase distribution transformer or three phase reactor loss, one phase shown negative watt loss. why??
What about electrical Units. discrive in detail
234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,
why using transformer and thyristor switch in 3 phase apfc panel
What is the difference between the transmission line and distribution line?
Define unilateral circuit?
I am about to write exam in RRB bangalore for the post of section engineer.please provide me with previous exam questions
can any one suggest paper presentation topies for electrical engg?
what is kondo syatem in eletrical traction
Why corona leads to production of Ozone and glow of the color VOILET?
operation of diesel generator