What are the various methods for effecive earthing in a
factory in a rocky terrain, where soil resistivity is
extraordinarily high? The usual method of 3 m deep earth
pits is not serving the purpose.
Answer Posted / brian
Import good black soil from some where else,mix it with alot
of salt and charcoal dust, dig atleast 2 pits in a space of
10metres apart.
Let each pit have its own earth mat and burry it wit the
mixture mentioned above ie salt, black soil and charcoal
dust and then bond or interconnect the earth mats wit an
earthwire of ATLEAST 35mm2.
Finally pour alot of water in the pits.
Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
hai now i am working as a electrical design engineer in construction field can i get a job in oil and gass field or power plant project as a electrical design engineer?
can any tell me why slope 40% and 80% is calculated in differential protection?
explain comutator action in detail.thanks
what will happen if earth of 33 kv cable (earthed system) is not connected to earthing pit?
what will be the maximum winding temperature of 6.6kv HT motor 450kw, Full load current 49A. 50Hz Frequency.
what is the major difference between LIBBP & HIBBP.. which one is most preferable..
what shall be no load voltage of 132/33 kV transformer ? is it 33 kv of 34.5 kV
If UG power cable both ends are to be earthed or what? If not why?
how to select automotive wire by mathematical equation with given current, vlotage and resistance
how to calculation increase capacitor,increase power factor for three phase.
What is 11 N1 and 12 N2 in single phase Transformer ?
What is the unit of magnetic flux density?
What is the RMS and DFT principle of analogue maesurments. Which way they are advangages. where which princples give optimum results.
mention hazard experienced during installation
I have been using an 600VA with 0.6 p.f UPS with my desktop which has 450W power supply unit. Can anyone explain how can this happen . Because the output of the UPS is 360W (600*0.6) (<450W)