what will happen if the secondary of current transformer
kept open....
Answer Posted / gourav
Transformers operate at nearly constant flux. The principle
of transformer states that in order to maintain practically
constant flux the emf induced by primary produces a current
in secondary (if loaded), which thereby opposes the cause
as per Lenz's law. If secondary is kept open, there will be
no opposition to induced emf. The situation worsens if it
is Step Up (CT) as heavy current in primary (load current)
will induce dangerously high emf across secondary leading
to saturation of core as well as hazardous situation for
working personnel.
This can also be explained by B-H curve.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
how net resistance islow in star connection and viseversa in delta connection...? if anybody could explain in detail it wud be helpful.
How to protect sensitive loads such as Dosing pumps inside a factory from voltage surge/voltage fluctuation.
I have 2 KW electric water heater.I am gonna use it in controlling water temp.so I needed to increase or decrease the heating capacity.is there any electrical-electronic circuit for varying the resistance & so current?
1. A bomber drops a bomb from an aircraft flying at 2000 km/hr. at an altitude of 7km. The speed at which the bomb will strike the earth would be
Role of active and reactive Power sharing in between two synchronized Generators, Droop Setting role ?
is it possible to say motor horsepower number without seeing name plate(when name plate damaged)
Why r u using pf panel. what the uses
Why syn. Generators are used for the production of electricity?
How to design inductive load for 3 phase 440v and maximum 5 amps for star or delta? Can we use a 15kW, 1450rpm motor for 15kW, 960rpm apllication?If yes.how......n.if thesame motor used what`s it`s sideeefect.
Earth is a conductor or load?then ammeter connect to 3- phase supply,it shows the measurents or not?
How does "OUT OF STEP" relay ,for Synchronous motor protection, work?
difference bewteen reverse current and alternating current
r we are using in gas turbine mark (5) frame (6) (made in india Bhel 1997) Ā
whati s the sludge current in ups
1. If 8.35%Z means the percentage impedance of 132kV-line from power company, we will like to reconfirm its base capacity.