how you can select circuit breaker for 2000kva transformer?
Answer Posted / foolinla
The capacity of a transformer depends on its rated voltage
and current. The load current varies depend on the voltage
of the transformer.
If this 3 phase 2000KVA has a primary voltage @ 4160V, then
the primary current is 278A (2000000/1.73/4160V)
If the secondary of this 2000KVA is 480/277 then the
secondary full load current is 2408A (2000000/1.73/480).
If the secondary of this 2000KVA is 208/120 then the
secondary full load current is 5558A (2000000/1.73/208).
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
c++ write a program to use a fuction call "max"which accepts an intger arrey of size5.as an arrument and return the larger and smallest of the arrey to main without changing. the original changing of the original position of the element of the arrey.
What is the function of auadag in a cro?
What is the maximum operating temperature for a thermoplastic insulated cable?
How to protect a Dosing pumps/any sensitive equipment (single phase) from surge protection inside a food factory.
how to convert lv line to hv line and viseversa, any losses will occur during this process
what is acceptable leakage current for 33kv cable while doing high voltage test for cable? how to calaulate the leakage current for 33kv or any rated cable?
Please sent me some previous year question papers of BSNL-JTO telecom and RRB in ELectrical Engineering to varshashahi@yahoo.com
What are the types of instrument transformer?
How to calculate multiplication factor in kva example 500kva ans pls ?
best manufacturer for busbar for outdoor switchyard having double bus bar scheme, can any one share technical specification of busbar. 132kv voltage ?
why do we have spikes enough to burn electronic boards, when generators are not grounded
in ring main system we use the isolater b/w transfer bus and main bus if we r not use isolatar than wat will be the effect in our sys.
what is the question paper model for section engineer in RRB
how much LT load can bear by the 100 KW HT connection.
I NEED RRB SYLABUS FOR JE ELECTRICAL ,PLEASE SEND TO MY E- MAIL ID joo28_eee@yahoo.co.in