6 MVA transformer secondary is rated for 725V at no load.
The incommer ACB is rated at 690 V, 3200 Amp. Would there
be any effect on performance of ACB due to lower voltage
rating?
Answer Posted / praveen kumar gupta
ACB is not suitable as transfomer secondary voltage level
is higher than ACB voltage level which cause insulation
failure of the ACB and cause of flash.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
How does cost of generation from hydropower plant compare with other sources of electricity?
What are the types of class b amplifier?
What facility we get after CT secondary earthing and how?
What are your personal skills and abilities for such a Master Course and your possible preparation to undertake this course?
Can anybody just suggest about the scope of Electrical design with ETAP software?Just guide me?
what is the pulse and audio frequency transformer? what is different between induction regulators and tap changing transformer?
whether starting current is limited to rated current of motor through soft starting or it exceeds the rated current?
What is an ideal transformer?
what is the isolation transformer. what is the isolator?
What are the protections for safe running of electric generator?
high voltage transformer input voltage,current and amps rating..distributed transformer input voltage,current and amps rating...
what is effect of 5amp fuse on 2mva pry protection of transformer
what are the differant std sizes of cable trenches?
What Should be the value of Vector Surge angle at Tripping and how to calculate it?
please tell me, how i clear the objective test? when i studied form the one book after i solved the objective ,that time i solved that qes. but if i tried solve objective form the other book then i could not solved these que.