can i know how to design overcurrent setting and earth
fault for 11kv & o.433kv system assuming tx 1000kva.

Answer Posted / prakash.

First selected for ct ratio in HT panel.1000kva transformer full load current in primary 52.5amps.so ct ratio in 60amps(60/5).
Now relay setting for over current 55amps.
And earth fault setting 0.5amps in ct secondary amps..

Is This Answer Correct ?    4 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to calculate fault level of 11 KV system

1509


What are the classifications of heating element?

1512


Two liquids hot and cold in two vessels are there and an metal bar acts as a conductor of heat between the two vessels. what happens then. what happens after 24 hrs?

1702


Explain Random and Deterministic signals?

1307


hi friends if you have any 400KV Substation Erection and installations Drgs please send to me.My email id:kandi.suresh441@gmail.com

2387






which types of relay used in acb and vcb?

2314


what is the need of starter in tube light and what type of starter is used in that?

1509


what is the advantages og idmt relay over magnetic relay??

3712


Ceiling Fan and Storage type water heater. Discuss

1543


What is inrush current? how can calculateit? what is the affect of it?

1533


what is the series parallel connection of capacitors? and how can we use these application in three phase motors for controlling torque?

1575


Is it a better option to procure screw type air compressor rather than reciprocating air compressor?If so, what is the reason?How should we select an air compressor(100 CFM)? Please mention the important parameters of air compressor.

1523


can u tell me the promotion from oiller to enginer

1419


salam&hi, i need to know about how can i calculate an enough current for the new building before i submit it to the suppliers

1611


As we use capacitor bank in 3ph ckt to improve PF, can we use capacitor in single ph domestric use, in house we have Fan,Mixer,electric cooker,iron,tube choke they also lag the system,because it is inductive load. if it is possible to improve PF of single ph system-- if yes- type of capacitor to be used,connection diagram, working in detail. if no-- list it.

1272