Hi ,what the accurate method to set correct(In) over load to
protect the 3~ motor
Answer Posted / pillay
I follow this method where before setting the overload
current setting I carry out an actual current consumption
test with a clamp ammeter.If the reading is lower than the
rated full load current of the motor I would set it at
actual reading add 5 percent and set it as the tripping
current. But if the the actual consumption is already the
rated fl current or almost it than the setting would be at
the rated full load current of the motor but never exceed
it.This way if it trips at any time than find out the root
cause and than only put into operation.
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
what should be the ideal gauge of wire (In sq mm) for different loads in Ampere?
primery try cell?
we all know voltage is a force(emf), and the force always devides if 2 or more than2 loads are there but why does the voltage remains same is parallel, it must devide na ???
What are approaches to tackle sedimentation problem of reservoir?
Explain RLC circuit?
how to calculate IR value of 33KV cable ??
1- What is the Polarization Index number be good for 15KV 3c#500MCM electrical cable? 2- Can I use the IEEE Std 43-2000 to perfom the PI test? Thanks
Can anyone provide with a SLD for HT panel installation for a 33KV line and distribution end has three 1.5MV transformers. Is it suitable to use OCB or VCB and also provide me the suitable rating and its connection diagram.
What is the purpose of using busbar mounting fuse?
What are stable systems?
what are the ''pitting rings''and how cn they be controlled in a series generator
What is the main use of rotary phase converter ?
How to select cable the size, what is the parameters use and what is the formulas use for this cable size calculation?
What is the difference between Delta & Wye windings?
how to erect roof control panel?