Hi ,what the accurate method to set correct(In) over load to
protect the 3~ motor
Answer Posted / pillay
I follow this method where before setting the overload
current setting I carry out an actual current consumption
test with a clamp ammeter.If the reading is lower than the
rated full load current of the motor I would set it at
actual reading add 5 percent and set it as the tripping
current. But if the the actual consumption is already the
rated fl current or almost it than the setting would be at
the rated full load current of the motor but never exceed
it.This way if it trips at any time than find out the root
cause and than only put into operation.
Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
What will be electrical cost per sqft for IT building (basebuild and fitout)and for residential township?
I have 4 DG set with 1500KVA rating. system breakers are 11KV & alternator are 415 Volts. Between alternator & breaker one stepup transformer used. i want to Know what is max. resistance for body earthing & 415 & 11KV V Neuteal earthing. my fault current is 14 times for 2 sec.
what is the total power generation in india?
is the value of inductance depends upon the evalue of thitha in doubly excited machine?
how do prepare ongc exam.how is it question model.i am electrical. which part covering in electrical.tell me
difference between high and low impedance BUS BAR relay??
Where is servomechanism used?
What does the kvar means?
how can we say that stator magnetic field rotates with synchronous speed?can we derive?
Why have to use copper cable for local isolator to motor ?
who can measure the size of power cable?
what kelvin's law ?
What is the minimum underground tank size capacity considered for firefighting purpose?
how to get electrical supervisour certificate in gujarat
What is the effect of atmospheric pressure & Temp; on efficiency of motor? Why NGR(Neutral Grounding Resistor) is used in 132/11 KV Transformer & how? What is the use of Auto T/F in Grid Station?