My requirement is 1VA,50/5A Current Transformer for
Metering .If I select 15VA , 50/5A CT.Is there any
possibility of Technical Problem ?

Answer Posted / roy

Hi ,
Yes there is . and a highr rated VA is never recommented
for metering ( again it depends the accuracy but still not
used as per IEC)
Note:The accuracy class will not be guaranteed for burdens
above rated burden or below 25% of the rated burden.Check
IEC 60044
Amd more interstingly , we are allowing or excepting to
saturate this metering core during fault to protect the
metering Equipment reff. IEC 44

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

After taking shutdown of 11kv feeder, if you see 5kv by phasing stick in the cable side, is it possible to close earth switch in cable.

1916


what is the function of gss in the dg set.

1478


How to connect the chemical earthing and complete process tell me plz

1395


11 kV line deraction check by an Engineer.

1525


Two liquids hot and cold in two vessels are there and an metal bar acts as a conductor of heat between the two vessels. what happens then. what happens after 24 hrs?

1709






State the types of distortions in amplifier?

683


Which level of the Transformer oil got dielectric strengh? And why?

1750


A Generator is in running condition and Rotor earth fault alarm is coming.How to check on line(i.e in running condition) whether there is actual earth fault in rotor or not.

1464


how can we find thae value of capacitor for single phase motor. what is difference between starting capacitor and running capacitor.

1884


what is the maximum temperature rating of a thhn insulated conductor?

1362


Explain what is electric traction? Explain few advantages of electric traction system?

613


For refrigerators the motor current is raised beyond its rating on both conditions when the voltage of the system is more(say 270v) than the rated voltage(220v) as well as when the voltage of system is less(say 160v) than normal voltageof 220v, why explain?

1524


What will be the voltage regulation of a full load and 0.80 power factor lagging load transformer when a two winding single phase transformer has a voltage regulation of 4.5% at full load and unity power factor?

743


Differentiate between ideal and non ideal current sources?

660


How would your past experience translate into success in this job?

6458