Answer Posted / k.prakashchandra
When the generators(gen) are connected to grid or net work
,if all the gens are run at unity pf ,there will be drop in
voltage due to inductive load in the system as the current
increases.Then to maintain system stability, LDC requests
large generating stations to increase the voltage . This
will increase the KVAR and results in lower lagging pf in
the gens. That is why the gens are designed for 0.8/0.85
pf.The pf of gens can be kept at any value by varying
excitation or resetting in APF mode.As pf control is
required by generating stations,capacitor banks are not used
.Capacitor banks can be used in the system to reduce the
inductive load but not in the gen stations.
| Is This Answer Correct ? | 18 Yes | 1 No |
Post New Answer View All Answers
What is the most accurate way of testing ELCB?ELCB is better than RCD?
How RTCC panel is working and give single line diagram for RTCC with transformer?
Name the component u would expect to find in a switchgear assembly?
1.what is difference between ATS & STS main use. 2.what is difference between ACB& VCB With symobles,and main partes, manimum range. 3.How many types of relays and main function.
Define newton's law of viscosity.
Explain Need of a starter in a dc motor.? Also explain any two starting and speed control method of dc motor?
what is the use of static frequency converter and static excitation equipment? and where it is employed? for what?
what is KSR type transmission tower? What is LSR type transmission tower?
Power factor =1.000 at factory in supply. However, PF = 0.8 at motor end. Current = 100 Amp, Voltage = 400 V. What is the power distribution loss? Can I reduce it by adding capacitor at the load feeder?
Classify drilling machines.
How to check the cable fault / hv test of transformer cable.
Why do power lines not short out when they fall into water?
What kinds of decision are made about CT from it's Knee point(voltage & current)?
briefly explain principle of resistance welding
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating