why capacitor bank is not used in generator power
Answer Posted / k.prakashchandra
When the generators(gen) are connected to grid or net work
,if all the gens are run at unity pf ,there will be drop in
voltage due to inductive load in the system as the current
increases.Then to maintain system stability, LDC requests
large generating stations to increase the voltage . This
will increase the KVAR and results in lower lagging pf in
the gens. That is why the gens are designed for 0.8/0.85
pf.The pf of gens can be kept at any value by varying
excitation or resetting in APF mode.As pf control is
required by generating stations,capacitor banks are not used
.Capacitor banks can be used in the system to reduce the
inductive load but not in the gen stations.
Is This Answer Correct ? | 18 Yes | 1 No |
Post New Answer View All Answers
will there be any problem by recovering slip from single phase induction motors?
is the value of inductance depends upon the value of thitha in doubly excited machine??
Define availability (operational)?
what is the relationship between current&voltage in practical purpose ?
Is there any standard guidelines/Criteria to design NGR/NGT.?
we specify current in case of feeder but in case of distributor voltage, why?
what is the importance of earthing system on the generators big capacity and small?
why the field winding in dc motor is not short circuited eventhough dc supply is applied across the winding
What is DTR erection?
WHY BREAKER ARE USED IN SUBSTATIONS?
Graphs of measuring power and speed on dc motor
what are factors to be consider in electrical installation like load factor,diversity factor .....
transformer phasor diagram under load explain it?
what is the prinsiple of dc motor and construction and working ,application of dc motor.
What is nichols chart?