Answer Posted / raveendra nath
PI value is the ratio of insulation resistance at 10
minutes to the 1 minute value...
PI = IR(10 min) / IR (1 min)
For good insulation, PI >= 2
PI more than 1.5 is acceptable...
PI less than <1 indicates Bad insulation
Is This Answer Correct ? | 8 Yes | 0 No |