why we use 20 KV, 10KA LA on 22 KV Line

Answer Posted / alok kumar nayak (action ispat

rating of la = line-to-line rms voltage X 1.1 X coefficient earthing = 22X1.1X0.8 = 19.36 =20

10 ka is nominal discharge current that means the surge current that flows trough ihe la after the spark over & it is expressed in crest value of spcife=ied wave (tested).
10ka < 66kv (lighting stroke is high)
5ka < 66kv(lighting stroke is low)
2.5ka > 22kv small substation
1.5ka > 22kv small trafo

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

hi friends if you have any 400KV Substation Erection and installations Drgs please send to me.My email id:kandi.suresh441@gmail.com

2391


How to design a Unit auxiliary transformer for a power house having a unit of 65 MW and Generating voltage of 11 KV and Secondary voltage of 433V

1662


How to find out damper winding failure for synchronous machine?

999


How to test lightning Arrester?

400


ho can we calculate the conductor insulation value according to their ratings like voltage,current etc.how insulation value related with voltage,current and power of amachine

1578






Do Phase angle measurement have any application in freq/harmonics measurement? If so how?

1462


Why we are using Isolation Power Transformer inplace of commercial power transformer? What's the difference between them?

1523


A system absorbs 100 k J of heat and the increase in its internal energy is 100 kJ; the work done is

765


What will happen if the d.c. Machine is operated below rated speed?

684


Sir 33kva 2 transformer load 900 amp calc 1800 amp mana jayega

1362


When color of silica gel will gets change from blue to pink from Top to bottom?

1119


how we can calculate the efficiency of a diesel generator ?

1159


Difference between Lugs and Thimbles

13751


What is the relationship between voltage,current & frequency?

1264


How to measure size of cable on a given load

1381