what is the procedure to carry out BDV test of a
transformer ?
Answer Posted / vinod
1)Take transformer oil sample from both bottom and top
section with suitable container on dry day
2)Adjust the BDV kit electrode for 2.5 mm and ceck with
gauge, increase the voltage till breakdown occur
3)Now a day automatic tester is available it will take
consicutive five readings with stiror. third reading will
be the BDV.
| Is This Answer Correct ? | 8 Yes | 3 No |
Post New Answer View All Answers
What is the rate of WCT on the Electrical Contracts comprising of DG Sets and Civil Works in Delhi ?
I want formula to calculate cable size as per load given in length & amp. I searched many sites but didn't right answer. Please reply me asap.
on a three-winding transformer relationship delta-delta-star, on third winding why the relationship is a star? what are the advantages and disadvantages? Thank you and please help
what is the maximum temperature rating of a thhn insulated conductor?
What is zero of the system?
sir i have cleared the apti test of EIL held on 15th march and my interview will be in new delhi on 2nd june.i will be very much helpful if u help me regarding the type of interview questions comes at EIL.(URGENT.........PLZZZZZZZZZZ...............)
how to test power transformer.YNd11
what is tri state logic gate
Briefing the effects of ASR and ACR of a double closed-loop speed regulating system.
what is the size of cable for 15kw motor and 85 meter cable length using with vfd
reason of diode failure in alternator
how to calculate fault level?
What is different bewteen low or high impedance busbar protection scheme
USE OF 8 WAY PAN ASSEMBLY
what is the path of thunderlightening? once both a buffalo and a person were standing 5m apart but lightening hit and killed buffalo not person?