we want install 11KV generator to supply power 12km far
from the power house.Load to be fed is 1MW.which conductor
should we use and wat will be transmission line losses?
Answer Posted / k.prakashchandra
The current is 52.5 A at unity pf, add 20 % .It is about 60
A. You can use Rabbit conductor
| Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
what is the best method of grounding in 30 MW generator?
what is the difference between RMS & TRUE RMS VOLTAGE
Witch do depand of Power factor and theory of power factor?
How can we calculate the KVA rating of a Distribution transformer from its core details?
What is Delta Connection? What is meant by Forward Delta & Reverse Delta & How Will be the Connection in Power Transformers?
types of central Air conditioner plant?
what is the minimum recommended leakage current of an earthed cable connected to the body or skid of an alternator
what are the differant std sizes of cable trenches?
If anyone would like to know or practice for FEWA papers contact me on mohamedrashad2@hotmail.com Just completed the supervisor exam in April 2021
I want to know Electrical Circuit?
What will happen if we introduce negative feedback to a control system that uses a positive feedback?
Why Neutral Isolation is required?
could an induction motor be used for regenerative braking in electric-train control? in this type of application would some scheme have to be devised to obtain low synchronous speeds while braking? would induction-motor drive, therefore, be suitable for passenger service?
Can I use distributon class/transmission class Lightning arresots for protecting the building? If not why please explain?
Pls tell me whether we can use EN3A material for shafts of Permanent magnet alternator.What will be the effect of magnetic and nonmagnetic material for shafts on magnetic properties of PM rotor .