How can we calibrate the level interface for Fisher®
FIELDVUE® DLC3000?if use water to calibrate and our liquid
SG are 0.75 and 1 ,Displacer height=14" and How much should
be set SG in trasmitter during calibrate,for URV and LRV
how shold be set

Answer Posted / iit

Calculation # If the calibrating liquid is water:
In the DLC3000 (Need Hart to communicate)
-ON Basic set up_PV set up set PV is Level
-ON Basic set up_PV set up set Specific Gravity =1
-ON Basic set up_PV set up_PV Rang set URV=14"and LRV=0".

1. First close both the primary isolation valves and drain
the liquid inside the chamber.
2. Fill water up to the center of lower flange level =0"
=0%
2.1 At DLC3000 on Basi set up_Sensor calibrate_Two Liquid
Lvl cal select Lower cal to get 0" =0% output
3. Fill it up to the center of the top flange level =14"
=100%
3.1 At DLC3000 on Basi set up_Sensor calibrate_Two Liquid
Lvl Cal select Upper cal to get 14" =100% output.
4. Fill it up to 50 %, check linearity.

After calibration completed with water and back on service
for interface
On DLC3000
-ON Basic set up_PV set up set PV is Interface
-ON Basic set up_PV set up set upper SG is 0.75,Lower SH=1.0
-ON Basic set up_PV set up_PV Rang set URV=14"and LRV=0".
and close drain valve and open both the primary isolation
valves unit ready to in service

Is This Answer Correct ?    8 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

in valve is constructed as per SME B 16.34, then which standard is used for fire testing of valve?.

1577


the pump holds on run indication into the dcs and filed local control panel remote push button condition operaton wrong like when the push button pushing conditions the pump is off and the push button release condition the pump is on totally opposite condition . And control room inside give the stop command into dcs just 1secon relay engage and again normal condition. How can I slove

1130


when placing a vent or drain hole on an orifice plate should you measure from the center of the bore up or down for the vent placement?

1304


How to convert Differential pressure to flow in TPH

1745


sir,would you please send me the Hindustan petroleum corporation limited papers(HPCL).my e-mail ID is ujjwal_sharma1983@yahoo.com

1815






What is the use of each wire in three wire RTD

2049


How will you test a transistor with a multimeter?

626


What is compensation for flow ? Why we use compensation ? What are the factors of different compensation ? We not use then what problems may happen ?

1477


How to calibrate RC Feeder system in thermal power station?,If any instrument available to calibrate it,ple inform me. make:stock,

2716


I WANT SECURITY PAPER MILL, HOSHANGABAD TEST PAPER.KINDLY SEND TO MY MAIL ID

2294


what is droop in governer ,type of droop ,how it work

1761


What is the difference between mmwc and mmwg?

850


What are continuances of connecting earthing and shield of branch cables (instrument to Junction box), at the same earthing pot provided on JB? Is it ok, or may produce some problem? 

2014


1. For Steam drum level signal, why do we compensate with drum pressure signal? 2.For main steam Flow signal is comensated with main steam temperature signal and main steam pressure signal why?

1775


what is piezoelectric transducer?give an example in power plant n state its principle?

2071