what is dyn 11

Answer Posted / dhiren

What do you mean by vector group of a transformer?
Ans:-
The vector group denotes the way in which the windings of a
transformer are connected and the phase position of their
respective voltage vectors.
The following examples are for two winding three phase
transformers:
So, what does Dd0, Dyn11, YNd5 etc. mean?
First symbol/symbols, capital letters: HV winding
connection.
Second symbol/symbols, small letters: LV winding
connection.
Third symbol, number: Phase displacement expressed as the
clock hour number.
The ANSI notations are not identical to the IEC marketplace
(See ANSI/IEEE Std C57.70). For the IEC marketplace the
winding connections are categorized as follows:
a) Delta (D,d)
b) Start (Y,y)
c) Interconnected Star (Z,z)
d) Open (III, iii)
Winding connection designations
High Voltage Always capital letters
Delta - D
Star - S
Interconnected star - Z
Neutral brought out - N
Low voltage Always small letters
Delta - d
Star - s
Interconnected star - z
Neutral brought out - n

Phase displacement
Phase rotation is always anti-clockwise. (international
adopted convention)
Use the hour indicator as the indicating phase displacement
angle. Because there are 12 hours on a clock, and a circle
consists out of 360°, each hour represents 30°.
Thus 1 = 30°, 2 = 60°, 3 = 90°, 6 = 180° and 12 = 0° or
360°.
The minute hand is set on 12 o'clock and replaces the line
to neutral voltage (sometimes imaginary) of the HV winding.
This position is always the reference point.
Because rotation is anti-clockwise, 1 = 30° lagging (LV
lags HV with 30°)and 11 = 330° lagging or 30° leading (LV
leads HV with 30°)
Dd0
Delta connected HV winding, delta connected LV winding, no
phase shift between HV and LV.
Dyn11
Delta connected HV winding, star connected LV winding with
neutral brought out, LV is leading HV with 30°
YNd5
Star connected HV winding with neutral brought out, delta
connected LV winding, LV lags HV with 150°
Some extra comments:
The phase-bushings on a three phase transformer are marked
either ABC, UVW or 123 (HV-side capital, LV-side small
letters)
Two winding, three phase transformers can be devided into
four main categories (Clock hour number and phase
displacement of those most frequently encountered in
practice in brackets)
Group I - (0 o'clock, 0°) - delta/delta, star/star
Group II - (6 o'clock, 180°) - delta/delta, star/star
Group III - (1 o'clock, -30°) - star/delta, delta/star
Group IV - (11 o'clock, +30°) - star/delta, delta/star
(Minus indicates LV lagging HV, plus indicates LV leading
HV)
Group I
Example: Dd0 (no phase displacement between HV and LV)
The conventional method is to connect the red phase on A/a,
Yellow phase on B/b, and the Blue phase on C/c. Other phase
displacements are possible with unconventional connections
(for instance red on b, yellow on c and blue on a) By doing
some unconventional connections externally on one side of
the trsf, an internal connected Dd0 transformer can be
changed either to a Dd4(-120°) or Dd8(+120°) connection.
The same is true for internal connected Dd4 or Dd8
transformers.
Group II
Example: Dd6 (180° displacement between HV and LV)
By doing some unconventional connections externally on one
side of the trsf, an internal connected Dd6 transformer can
be changed either to a Dd2(-60°) or Dd10(+60°) connection.
Group III
Example: Dyn1 (-30° displacement between HV and LV)
By doing some unconventional connections externally on one
side of the trsf, an internal connected Dyn1 transformer
can be changed either to a Dyn5(-150°) or Dyn9(+90°)
connection.
Group IV
Example: Dyn11 (+30° displacement between HV and LV)
By doing some unconventional connections externally on one
side of the trsf, an internal connected Dyn11 transformer
can be changed either to a Dyn7(+150°) or Dyn3(-90°)
connection.
Additional Note
By doing some unconventional connections externally on both
sides of the trsf, an internal connected groupIII or
groupIV transformer can be changed to any of these two
groups. Thus, an internal connected Dyn1 transformer can be
changed to either a: Dyn3, Dyn5, Dyn7, Dyn9 or Dyn11
transformer, by doing external changes on both sides of the
trsf. This is just true for star/delta or delta/star
connections.
Changes for delta/delta or star/star transformers between
groupI and groupII can just be done internally.

Is This Answer Correct ?    15 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Difference between a pilot wire and a normal conductor?

1567


how are reversing the direction of rotation of dc motor

1256


what happen if field of dc shunt motor opens? what is function of putting res. in parallel to one phase of 3 phase IM? the power supplied by 5A source in circuit is given by------Watt.

1548


how to discharge 3 phase power factor correction capacitors

1956


volts=230 c=10mf a=??

1571






I have done my m.tech in electrical engg discipline. Can any one please suggest me how should I prepare for getting into phd in iit or nit.How should I prepare for getting into lecturership

1200


working principle of AC Servo Motor with its construction

8330


how we arrange the hv side with delta connection in case 33/11kv of transformer.

1534


How Self works in DG set

1404


what are the disadvantages in GIS over AIS

1914


a 100mva,400/200v transformer has leakage impdce of 10% draws a steady state line currentof---------------

1450


is there any lightning by passer is arranged in ship like buildings?

1464


pls tell what are doing the three phase motor star and delta connetion with circuit diagram and control wiring .

1457


hi i have applied for lic of india south cenrtal zonal ,hyd. i didnt get hall ticket till now.let me know how can i get form internet

1469


We have Diesel generator of 200KW. fuel consumption is always same,even connected light load or full load. Is it right?

1735