Dear Friends,
I have a 500KVA transformer supplying whole factory having
3 phase and single phase mixed loads. Power room has
ammeters connected via CTs for individual phase. Now I know
that readings shown on meter for each phase say R,Y and B
are line currents. But when I want to know the total on
transformer do I need to add the currents of all three
phases readings shown on meter or value for anyone phase
will give me the correct power load on transformer for that
point of time.
2. If ammeter shows unbalanced readings for R,Y, B phases
say 150, 250 and 300 respectively so can I assume that 150A
i.e average of 3 will be the 3phase load currents and
remaining will be 1phase currents. Please clarify my doubt.
Answer Posted / ahmadmukhtiar
1. The load of R, Y or B will be the total load on
transformer.
2. There must be phase balancing system for protection
otherwise the equipment connected as load will get damaged
if all three phases are unequal.
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What are locations arc protection relay is fixed.
How to calculate KVA/VA rating of PT or CT from primary & secondary voltage or primary & secondary current?
magnetizer priciple
What is meant by earthhing of a magnetic flow meter and when to use empty pipe detection?
HOW WE CAN REDUCE THE CIRCUIT COMPLEX OF STAR-DELTA STARTER .BECAUSE NOW WE USING ONE TIMER RELAY & THREE CONTACTOR FOR MAIN,STAR & DELTA ?IF ANY IDEAS PLZ POST.THANK U
Why you want to join non technical field when you are an engineer?
Electronic circuit
why asa method ZPF method is more accurate than ASA method?
PLZ sent the previous year question paper for GET in NHPC on my EMail id ppshanker@gmail.com
hi friend i am going too attend for hpcl in this month please help me by sending written test question papers i am in the stream of E.E.E
I need model question papers for RRB section engineer Chennai... Please send to my E-mail Id:- maitheerainbow@gmail.com
How can we find out LT UG cable fault (size,from-4*25mm sqr to 4*300mm sqr)? How mani types UG cable faults?
What is the formula for selecting the cabels according to load? How to calculate what sq.mm cabel to be used?
What is the Good Earth resistance value of G.I & Cu. Chemical Earthing & Normal Pipe Earthing?
what is the difference between rectifier and converter and commudator?