We have a 33/11kv switchyard having 12.5 MVA power
transformer. We export & import power through this
transformer. When we export power, the PF will be depend on
GRID PF & when we import power the PF will be depend on our
load PF. but the problem is that,when neither we export nor
import but our 33KV vCB is in close position,our meter read
the power factor 0.14 to 0.25 at that moment. So how can be
we improve the power factor at that moment.
Answer Posted / k.prakashchandra
You should realise that when there is no load on
transformer, the pf is almost zero
Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
What is current divider rule (cdr)?
what is meant by moulded case circuit breaker ?
what is the best transformer oil breakdown voltage?
At what factor resistance r of a conductor depends?
Role of active and reactive Power sharing in between two synchronized Generators, Droop Setting role ?
What is transient Phenomenon?
we have amp, voltage, kw, length detail then how to calculte copper & alluminium size of conductor of 3-phase induction motor
We need to current density & short circuit calculation at 65kA for aluminium & copper busbar.
what is the significance of terminal voltage and phase sequence in the operation of paralleling of two generators?
WHAT IS ELECTRICAL MAINTAINTENCE ?
What are m circles?
sir i have a car stereo system and there is jack on him so can u tell me a way to find out their power terminals on the jack or on the circuit board"
What will be the current drawn by HT motor, if low voltage is applied.. any formula to calculate the LT amps of HT motor.?
i need of the bhel question papers along with answers and also give some website names for the downloading question (electrical and electronics engg question)please help me....
Y phase plates are used in transmission line??? what is there need???