how to claculate earth strip size for 1500kVA transformer
for neutral and body
Answer Posted / bala.a
you will follow as per State electricity board norms - 50
x 6 mm Cu for Nu and 50 x 6 mm GI FOR body 0r
you will calculate as per short circuit calculation
Formula 0.0054 x root t x I
Where
t =1 second
I = SHORT CIRCUIT CURRENT
example
Fault current- 33kA( assumed )
0.0054 x root 1 x 33000= 178.2 mm
so you will recommended 50 x 4 mm Cu
Is This Answer Correct ? | 14 Yes | 9 No |
Post New Answer View All Answers
Usually in the L & T make MCC feeders' power circuit,we have BMR after the MAIN CONTACTOR.,can we interchange their position, keeping the control logic same???
if there is nutral in phase why we use earthing wire and grounding? even at fault condition the fault current flows to neutral (it is a lower path)
why they were using TRIAC instead relay in some controllers and what is the advantages.
what is the Transformer Impedence?How can calculate?
State angle criterion.
Does all the output contacts (N/O as well as N/C) of a Numerical relay operate when relay receives a binary input/inputs or contacts are designated to specific logic input/inputs and only these contacts operate?
DC transmission
I have iti elec, 1st aid, and 5 yrs experience in 7.5 mw power plant. Am i eligeble for 11kv license in telangana state..when, how to apply for that.?
what are the applications of TIG welding
What is the de rating factor of cable? What is the importance of the de rating factor in cable selection?
at what basis/standard we have to arrive the current density of aluminium/ copper in busbar?
what is the size of ht cable of 33kv ht line and transformers ratings are 1 Mva and 5mva.please send formula also.
why ht motors are star connected?
What is the purpose of using busbar mounting fuse?
What the formula for calculating no.of earthings & size of earth strip for 100mX90m shop.