How to calculate HT XLPE CABLE for 11 kv / 433 v , 1500 kva
oil type transformer system?
plz provide step by step calculation

Answer Posted / madhu mohan

First calculate the current of primary side(HT) and derate the cable by atleast 0.7.
Eg:1500*1000/(1.732*11000)=78.73A
Current I after Derating =78.73/.7 =112A (0.7 if laid on the trays or value will vary if buried in the ground).
Cable equivalent to rating has to be selected.
Now Short circuit withstand capacity (sq. of I X t in sec) has to be checked from the cable catalogue.This value of cable should be higher then SC withstand capacity of the ground usually it is 50KA.it less go for next size and finalise.

Is This Answer Correct ?    32 Yes 24 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Define maximum demand?

648


If short circuit ratio is high is it bad or good for a machine then tell the reason...

1594


all details of DG UPS HVAC

1528


what happens when series resonance occurs?

1388


ANY ONE TELL ME ABOUT generator synchronization panel panel to synchronise 3 gen of 250kva both automatic and manual. 2 gen output vol 415 3ph, 1 gen output vol 400 3ph SEND THE DETAILS DIAGRAM ON THIS EMAIL ADDRESS ayazleo@hotmail.com as soon as possilble best ragrds electrical engineer ayaz mahmood SAUDI TECH

3699






In siemens S7-300 PLC, what is function and function block ? What is the difference between them ? When to use function and when to use function block ?

2650


How can we find the breaking capacity of a Load breaker switch (LBS) fed from 11 kv supply??ex:50KA, 26kA etc???detailed step vice answer pls.

1583


please send 5yearje solved papers on my email himmatsinghnathawat@gmail.com

1470


what is x'mer ,isolation x'mer & yltra-isolation x'mer?????

1835


For refrigerators the motor current is raised beyond its rating on both conditions when the voltage of the system is more(say 270v) than the rated voltage(220v) as well as when the voltage of system is less(say 160v) than normal voltageof 220v, why explain?

1519


how is the connection of a 3 phase ct trivector meter done on a pole mounted transformer

908


There is any especial requirement for motor to drive through with VFD?

2173


what is the difference between circular wdg & ractangular wdg?

1554


What will be the impact on motor performance if a LT motor is rewound with changed motor winding data as given below:- Original winding data: total 04 wires = 02 wires of 17 SWG + 02 wires of 16.5 SWG. Changed Winding data: total 03 wires of 15.5 SWG wire size Motor rating: 160KW, 740RPM, 415V, ID FAN application. Normal Running Current = 95% of FL Current.

1578


sir plz send some previous year questions of jspl.

1475