If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.

Answer Posted / virendra joshi

Dear friends,


Total Connected Load = 375 KW
KVA required @0.8 PF = 375 /0.8 = 468
Taking a 0.8 as a Demand Factor = 468 *0.8=375 KVA
Considering running of D.G set on 80% load = 3750.8=468 KVA
Considering 20% load for future expansion = 468 + 20%(93KVA)
Total KVA of D.G set = 561 KVA

you can go with 600 KVA D.G set .

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

The windings of a transformer are divided into several coils, because?

816


How to calculate pitch, gauge of winding wire, and No. of turns for 30HP, 3 phase, 4 poles 50Hz, 380V induction motors

1481


Who many reason of ignition fail ?

1476


What is transient Phenomenon?

1782


if main CT is of ratio 50/5, and meter CT is -/5 what will be overall multiplying factor of meter.PT is 11000/110 .

1160






if voltage bt phase & nutral is 38v in a panel board . whats the root cause.

1821


at what base you will tell the direction of rotation of dc motors and generators?

667


What are the advantages of stationary armature and rotating field system?

704


Write down the name of 2 lady Bir Pratin of Bangladesh

1566


Why does the adjacent zone of protection overlap?

694


If we connect a motor and generator together (I mean that the generator gives the motor electricity and the motor gives the generator movement) regardless the losses. Will the generator still generate and the motor still move?

1701


what is LSR?

1720


how give earthing conection to household equipment?

1499


salam,hi, i need to know what the spesification of 300amp msb...

1597


What is the meaning of Insulation H for transformers????

1615