If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / virendra joshi
Dear friends,
Total Connected Load = 375 KW
KVA required @0.8 PF = 375 /0.8 = 468
Taking a 0.8 as a Demand Factor = 468 *0.8=375 KVA
Considering running of D.G set on 80% load = 3750.8=468 KVA
Considering 20% load for future expansion = 468 + 20%(93KVA)
Total KVA of D.G set = 561 KVA
you can go with 600 KVA D.G set .
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
The windings of a transformer are divided into several coils, because?
How to calculate pitch, gauge of winding wire, and No. of turns for 30HP, 3 phase, 4 poles 50Hz, 380V induction motors
Who many reason of ignition fail ?
What is transient Phenomenon?
if main CT is of ratio 50/5, and meter CT is -/5 what will be overall multiplying factor of meter.PT is 11000/110 .
if voltage bt phase & nutral is 38v in a panel board . whats the root cause.
at what base you will tell the direction of rotation of dc motors and generators?
What are the advantages of stationary armature and rotating field system?
Write down the name of 2 lady Bir Pratin of Bangladesh
Why does the adjacent zone of protection overlap?
If we connect a motor and generator together (I mean that the generator gives the motor electricity and the motor gives the generator movement) regardless the losses. Will the generator still generate and the motor still move?
what is LSR?
how give earthing conection to household equipment?
salam,hi, i need to know what the spesification of 300amp msb...
What is the meaning of Insulation H for transformers????