Dear sir/mam
Iwant complete details of Naintenence of 33kv/433v
Transformer having 1250 KVa
Answer Posted / virendra1981
Dear friend,
In routing maintenance you should take care of the
following .
Daily .
1. Percentage loading of a transfomer
2. Make sure the bucholze realy is full with oil no inert
gas is there if there then purge the same.
3. Check the record the Reading of OT & WT
4. Check manualy for any leakage from any part of the
transformer.
5. Check for any abnormal heating & noice in transformer.
Quarterly.
1. Check & change the silica gel of the breather .
2. Check teh Safety function tripping of HT breaker related
to transformer. ( tripping point of OT , WT & Tranfomer )
Annualy.
1. Check & fillter the Trasformer oil
2. with complete shut down take the reading of insulation
resistance of the transformer winding.
3. Open & check the condition of transformer HT & LT
bushing for any cracks or damage.
4. Chceck the condition of the earthing pit & take the
earthing resistance value for all the earthing pit (
Neutral & Body earth )
Do the same as directed & have a trouble free operation of
the transformer for a long period of time
Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
Please explain me about Relay curves and their sources to read ?
What should be the length of transmission line so that we can see/obtain the full sine wave of voltage??
What are the types of excitation system?
What is the maximum operating temperature for a thermoplastic insulated cable?
our factory is going under construction mean time transformer 1000 kva 2 nos &load break swithch 12 kv & 4 nos 750 kva 2 nos & 380 kva 2 nos generator to be errcted.how to arrange earth pits &how to earth connect & neutral pit how to calculate in earth bit size.
we need a ntpc previous papers
What are reasond for high wattage in single phase induction motors
what is the difference between earthing and unearth
Briefing the effects of ASR and ACR of a double closed-loop speed regulating system.
what is rocking arrangement in arc heating
The knee point of a current transformer is normally unique and known.So why in the nameplate of a CT they put the minimum value like this Vk> 400v.
what is effect of leading power facter on the system and billing
a 100mva,400/200v transformer has leakage impdce of 10% draws a steady state line currentof---------------
how we can explain arc heatng?
what is vtg limit of earth and neutral at transformer side?