in 132 kv substation ligtning arrestor(120 kv) connected to
line. but line voltage comes to 132 kv, it operate or
not???

Answer Posted / vettum perumal

Ligtning Arrestors are connected across one phase and
earth. Hence,the insulation of the arrestor shall be
suitable for only phase voltage. that is, 132kv/root3 =
76KV.Hence, these 120 KV LA will operate very well.

Is This Answer Correct ?    26 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

i want to put single phase load on scott connected transformer,eventhough how to balance the transformer.

1414


what type of motor used to move a 1 ton gate? and relate ratings with load.

1350


Sir pl provide 5 year sample paper for post junior engineer(electrical).I have currently applied for junior engineer (electrical) on RRB Ajmer

3191


Why computer humming sound occurred in ht transmission line?

657


How can we calculate cable size in Low voltage & high voltage

1157






In between UPS out going changer over switch and ups raising main input, both side cable gland producing heat but the cable doesn't get heat,Why?

1719


how to setting voltage RTCC panel

1212


What is the minimum distance to be maintained in between HT panel and LT panel and Instrument panel as per IEC and NEC standards?

1240


what is the common earth

627


Explain the functioning of diode?

655


why does the magnetic balance tests at transformer?

1420


How to synchoronize the generator (with gcb,GT) to grid????? ????? from Grid iam getting power (rated 400kv/20kv) through GT and its goes to UAT.,,ST.,, now my generator(rated 20kv ) ready.,, now iam closing my GCB.,, in GT iam suddenly giving 20kv on that Gt.,, what will happend

1623


1)What is a Triode? What are its uses? 2) What is a Triac? 3) What is a Thyristor?

2067


why the rotor current becomes in steady state during high slip region? please verify with equations.

1560


Explain using drawings what is reverse PID action w.r.t PID controllers.

2751