i have one transformer 1000kva, 11/.433kv. we are using
200/5 amp. ct unit for measuring purpose, & one 800 amp.
V.C.B Unit for the same t/f operate, i wants to known the primary
current of T/F is only 53 amp. why we used 800 amp.
V.C.B ? & 200/5 amp. CT Unit.
Answer Posted / vinit patil
You are right, you should fight with your electricity board
regarding the HT Metering CT ratio. You should actually
required 100/5 ratio.
But while deasigning VCB it is always prfarable to go on
higher side because it can sustain the heavy short circuit
current. One thing should be noticed that the protection
CTs should be as per the Primary current of the ransformer.
Is This Answer Correct ? | 5 Yes | 2 No |
Post New Answer View All Answers
How o select the electrical fuse?.What are its characteristics.How to select the material od fuse?
how to calculate voltage drop and followed by cable calculation?is there avail in formula?
What are the advantage of free wheeling diode in a full wave rectifier?
how choose conductor&depending upon load
what should be the no load current for 3 phase ac motors ranging from 5 kw to 1000kw?
how to select size of hardware for linking aluminium busbar is it depend on area of busbar or current flowing through bus bar
why ct ,cvt should be stored in a vertical position?
what is the necessity of under ground cables ??
what is lumped and distributed elements?
What is the operating principle of turbo-generator.
Why compensation is necessary in feedback control system?
STATE USE OF ARC RUNNERS & SPLITTERS ?
what is the calculation formula for motor starting torque,running torque, running torque.
how to check regenerative load in drived motor
i need project topics along with circuit diagram in the electrical and electronics engg and also some websites regarding projets.