How much KVAr bank reqired for 630 KVA transformer on full
load for maintain power factor upto.99

Answer Posted / dhanesh koshti

Capacitor calculation is depends on load. if 630 KVA transformer is loaded fully with load p.f.=1 then no compansation is required but if the same is fully loaded with load p.f. = 0.8 then, kvar required is calculated as below:
KVAR = KW ( tanǾ1-tanǾ2); Ǿ1=old p.f.angle, Ǿ2=new pf angle

= 504 ( 0.75 - 0.14) [ here, KW=504 because, 630 X 0.8 = 504]
= 307.44 KVAR
say, 300 KVAR bank is required at load end for compansation

Is This Answer Correct ?    15 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Why power genaration in India is at 50HZ while America its 60HZ

1865


What should be the amps for a MV fuses for transformer 630kVA 20(10)/0.4 kV

1588


what is the interrelation between voltage current torgue speed and magnetic flux in case of different types of electric motors

1521


how to calculate insulation level of transformer?

1086


how to identify conection leads of an unknown electric motor

1548






can we use trip light with bus coupler?

1429


What are high pass filter and low pass filter? and What are the flowmeter ?

1501


What is rotating magnetic field?Discuss elaborately.

2140


Define settling time.

709


what is a speed of rotor when we give supply to stator of 50hz and as well as rotor of 60hz of an induction motor?????

1223


what is doubling factor in making current of a breaker?

1553


why impedance relay is used for medium transmission line protection

1797


what is kondo syatem in eletrical traction

1657


how to synchronize 3 phase slip ring induction motors of different ratings.

1779


What are books to be referred for KPTCL exam?

3215