there is one orifice plate already installed on 3" line, but
my previous engineer(who is not working here) removed that
tx, but now i want to take it in to the process, so now what
i have to do now? flow fluid is hytherm oil of temp. 260deg
& pressure is 3bar.
Answer Posted / sam
In any industrial plant there will always be good records
and documentation on all equipment as well as all
instrumentation installed on the plant. The easiest in your
case is to find the FT tag number on the P&ID drawings or
the CCR faceplate and look at the data sheet of the missing
transmitter. The original calibration in differential
pressure will be on there as well as the model number of the
transmitter you need.
All you then have to do is calibrate the new DPT with the
diff press as per the data sheet and it will work as before.
In most cases the squire root extraction is done in the DCS
and not in the transmitter so try it just like this first.
The faceplate in the CCR will normally be set up to display
the min and max flow so that will not help you to find the
calibration diff pressure of the transmitter.
You can also try and find the original transmitter that was
removed and put power on it ans see what it was calibrated
for before. Even if the transmitter is faulty it might still
be able to display information. The is just as a last resort
since you cannot be sure if this calibration is what it
should be and it is better to double check it with the
documentation. This is just a method to double check
information.
As a desperate measure you can also measure the upstream and
downstream pressure as it is now during normal operation and
calibrate your transmitter to 1,5 that differential pressure.
For example:
Say your upstream pressure before the orifice is 300Kpa and
downstream it is 270Kpa you therefore have a DP over the
orifice of 30Kpa during normal operation.
Calibrate the transmitter for 0 to 45Kpa.
The flow indication inside the CCR will indicate the correct
flow since the extraction and the display is already setup
as it was originally. Have a look at what the % the flow is
indicated on the CCR faceplate. Since it is normal
operations it should be about 50% of the scale on the
faceplate. If it is not, modify the DPT calibration until
the current flow display about 50% of the full scale in the
CCR. You should be pretty close then.
This is not a very good or accurate way to do it and you
should keep on looking for the original design specs and
then re-calibrate the DPT when you found it.
Good luck
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
How to find out the current of two motors having same power consumption but different RPM?
What is stripper & spilitter ? Diffrence in this.?
KAlman filter code for two dimension?
basic connection and principle of axial shift sensor n differential sensors in tubine describes n draw......
How to work togather like sov,limit switch,proxy switch and booster in xv
Capacitance, resistance ( colour coding ), parallel & series circuits.
where i can get training in INTOOLS and PDMS in Delhi-NCR OR north part of India. please reply with ur ans. at arunsamkaria@ymail.com
how to tune siemens sipart electro pneumatic positioner..plz tel me..
how to calibrate and troubleshooting of leveltroll?
Explain the difference between mmwc and mmwg?
find the kp ki kd from the transper function G(S)=29.44s+04707/1.5349s2+s
Explain the working of an electronic level troll.
How is work 5/2 sov?
What are de-saturators?
what is orfics working in main steam line. is it increase pressure, velocity of steam flow and dicrease steam flow rate. or any other