What is the acceptance value of leakage current in HI POT test
Answer Posted / c.hari balakrishnan
SWITCHGEAR : -
There is no specified value of leakage current,Normally it
depends on how much load is connected.Normally it is in
milliamps.For example : In 11kV SWGR we highpot with 20bays
(indoor SWGR)we can get around 20 to 30 mAmps...
Cable: -
for cables normally we can get around very low Milliamps...
| Is This Answer Correct ? | 8 Yes | 8 No |
Post New Answer View All Answers
What is essential to prove safe isolation of electrical circuit?
WHY THE DIMENSION OF TWO SAME RATED MACHINE IS DIFFERENT ?
List the advantages of star-delta starter with induction motor?
What are the Full Forms of TVM, MTL, CVT ?
Why have to use copper cable for local isolator to motor ?
explain the process of commutation in a dc machine. Explain what are inter-poles and why they are required in a dc machine.
how does it help for selection of a transformer.
There are a trformer and an induction machine. Those two have the same supply. For which device the load current will be maximum? And why?
how to test YNyn0 vector group in transformer?
TELL ME WHAT IS INDUCTOR AND CAPACITOR WHAT IS IT BASIC OPERATION ANDFUNCTION?
In synchronous motor, how the field current is related to armature current..i know its inversely proportional..but concept wise...i was nt clear....pls help me...
is this the formula of building wiring to get the main breaker.Watts/volts*.8%+higher motor*(25%)=ampere. yes or no or send the correct formula for building wiring.
1. What is maximum permissible distance between smoke detectors ? 2. How do we decide number of smoke detectors required in a large office, warehouse, hall etc ? 3. What should be maximum height of smoke detectors ? 4. Where do we use heat detector, optical smoke detector, temperature sensitive detector ?
I need to connect a synchronous generator to the grid using automatic synchronization and two circuit breakers (one for synchronization, one for end connection to the grid), how to determinate the required diameter of the cables?
for hipot test on 33kV busbar, we will test on 70 kV or 56kV, what is the acceptable leackage current?