how to choose the cable rating for load (KW)? EXAMPLE.50KW load
Answer Posted / mohammad farman khan
Fisrt calcultate Load in Ampere as basic formula below
I (Amp ) = P ( KW) / 1.732*Voltage (400 or 415 or 380 )*
p.f
Voltage depend on frequency rating (50 Hz or 60 Hz)
then check where you have to laid in AIR or Ground
you have to consider so many factor.
suppose you laid in Ground then factor to be consider as
below
(1) Soil Thermal Rseistivity
(2) Group factor
(3)Rating factor of ground temprature
(4)Rating Factor depth of laying
then calculte Voltage drop on behalf of amper rating by
load.
once you calculate then check length
V.D = mv x I X L/1000 OR mv =V.D X 1000/IXL
VD= Maximum acceptable volt drop (in volt)
mv =appropriate volt drop (in mv /amp /metre
I = Current per phase (in ampere)
L= Length ( in meter)
Is This Answer Correct ? | 50 Yes | 15 No |
Post New Answer View All Answers
how to determine the cable size...pls explain me with the formula taking particular load....does the factors like impedance & short circuit rating influence the cable size, if so how....
i want design of D.C.MOTOR 1HP 960RPM AND 2HP 960RPM ITS URRGENT
at which voltage level arcing ground is occurs ??????????
what is plunger and what's the use of it in motor alignment?
Why different Pressure switch used in marine boiler water circulation system
Working of microwave oven?
how to set relay setting? and example calculation...
What is a compensator?
explain different types of d.c motors?
WHAT IS LOAD CELL
What should be the voltage between Neutral and Ground in secondary side of the step down transformer (230 V to 110 V) with no load condition?
While HT line put on to activate ACB in low tention panel VCB tripping instantly.why it happens
distribution is maximum done by a)radial b)network c) parallel d)b & c
What are the advantage of free wheeling diode in a full wave rectifier?
We have 110Vac ,10A ac supply which is converted into 110VDC & How much DC current? which factor is reqired for dc current calulation?