If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / munish saini
KW=KVA*PF
PF=.8
KW=375
KVA=KW/PF,=375/.8=468.75KVA
20 Percent required more as eppiciency Factor
so required dg should be=562.5 KVA
| Is This Answer Correct ? | 4 Yes | 1 No |
Post New Answer View All Answers
What is the bundle conductor?
IF alternator SCR value will be high means what happen in alternator efficency at operating power factor of 0.8
How to test the vector group of a Yd11 transformer? what are the relations to be checked between various vectors to confirm this vector group?
1.Can we use 6.6/11KV 300sq mm xlpe 3core cable for LT use (415 Volt). 2. If we use it for LT then what is the current rating
My question is abt backlog.I had dropped one subject in my second year, and completed this subject in the 3rd attempt, so how many backlogs i have got?1 or 3?plz sujjest the answer as soon as possible
HOW TO CALCULATE THE REGULATION OF 100 AND 25 KVA TRANSFORMER
What does bode plots shows?
How to calulate Locked rotor amper(LRA) for compressor type motors?
If rotor works in clock wise what happens
Is RTCC panel needs any control supply.
what are the sample questions asking to the test cunducting for electrical superwising lisence test?
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
What is size 00, 01, 1 etc., in HRC fuse types?
What is the typical enclosure type used for Indoor switchgear / Outdoor switchgear Units? - In Onshore / offshore Units?
what are the safety measures of induction motor?