Classical power system stability was mainly focussed on
rotor angle stability but modern power system stability has
more focus on voltage stability.Why?
Answer Posted / iamdon
Majority of blackout/grid failure now a days is due to
voltage instability phenomenon.
This is because Modern power system is very vast and
interconnected to form a grid network.Also generation is
not sufficient to meet the load demand which is incresing
rapidly, due to which load end voltage drops.To maintain
load end voltage and power factor within permissible limits
shunt capacitors are used extesively at almost all load bus
bars(Over compensation),which has detrimental effect on
voltage stability.
At the time of peak load(load increase),the voltage at the
load end decreased so reactive power supplied by shunt
capacitors also reduced.So when we have most need of
reactive power supply,the shunt capacitor prove less
capable.
That's why modern power system satbility problem shifts
towards voltage stability.
Author:arbelectbit@yahoo.com
Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
In HI POT test what is reason for applying the AC VOLTS and DC VOLTS in different applications what is the nessesity for this ?
What do you mean by pull of electromagnet?
8. A DYNAMOMETER TYPE WATTMETER RESPONDS TO THE.......
why would the rotor rotate at sub synchronous speed against the direction of rotating flux when d rotor of 3 phase IM is connected to 3 phase balanced supply and the stator windings are shortcircuited ??
why a tester wont shock while testing the power in house
Define cut-off rate?
What is mean by spike arrester(Voltage Operated)
what is thresold of perception
Transformer diagram mention each parts ?
Types of test in Switchgears, MCC, NGR and DB's how it should be procced. Can anyone give me the details here or email me to pasuvaraj.k@gmail.com
Why derivative controller is not used in control systems?
is it value of power factor is more than unit. whats effects in the source supply
75 kw motor take 45 amp in no load delta in star 10 amp but in load it will take 160 amp but IR velue of winding above 500 at 1kw ph to earth and ph to ph. what problem it should be?
what is zinc diffusion?
howmany electrician should maintain for a 1000 kva used plant... in kerala..