Assume a condition such that two motors of rating
6.6kv,415v are connected to blower,so tell me which motor
draw large current give appropriate reason?
Answer Posted / pillay
The current drawn depends on the power consumed by the motor
and the operating voltage.
KW =1.72 X VL X IL X PF
Now assuming both the motors are loaded at 100 kw each OF PF
0.8 than the 6.6kv motors current consumption will be
100000KW /1.72 X 6600 X 0.8 =11 AMPS
If 415 volts is used than
100000 / 1.72 x 415 x 0.8 = 175 AMPS.
Is This Answer Correct ? | 17 Yes | 1 No |
Post New Answer View All Answers
A cotter joint is generally used to transmit
Why the moulded plug comes with domestic appliances instead of assembled plug like anchor, Vinay 5/15 A.
How to calculate Ith (I thermal) for curent transformer
could anybody able 2 send me jindal steels previous papers fr electrical steam....pls send 2 my id if possible....sirisha.shaik@gmail.com
What is the minimum underground tank size capacity considered for firefighting purpose?
I have 4 DG set with 1500KVA rating. system breakers are 11KV & alternator are 415 Volts. Between alternator & breaker one stepup transformer used. i want to Know what is max. resistance for body earthing & 415 & 11KV V Neuteal earthing. my fault current is 14 times for 2 sec.
how we design a pannel to start 10HP motor with the help of star delta starter?
what are the sample questions asking to the test cunducting for electrical superwising lisence test?
What is formula calculation size cable wire ?
What is an alternator impedance value?
Mention the disadvantages of low power factor?
In electrical what is earth(ground)connection, wht is the importance of it, why it is recomended to maitain below 3VAC between Neutral and earthspecially in PLC used machines?
The electrical energy required to raise the tempreture of a given amount water is 200 kwh. If the heat losses are 20%, the energy required is?
what the Microsoft .NET framework is?
What is non-minimum phase transfer function?