Hai I have 2500KVA,Transformer,13.8KV/380.DELTA/STAR.How
much load that I can take interms of current?How can I
calculate also when I have loads in KW?
Answer Posted / saqib haroon
as per my point of view,answer of the input current is
wrong. Why the respectable brother put power factore value
with KVA rating, as per formula only once we will put PF
value, which will divide this KVA rating.
In this case the answer will be
P1= 1.73*V1*I1*cosphi
2500= 1.73*13.8*I1*0.8
2500/1.73*13.8*0.8= I1
131 A = I1
Remaining portion is OK
| Is This Answer Correct ? | 3 Yes | 5 No |
Post New Answer View All Answers
what is the function of impulse relay
A 100 kVA , 400 v/250 kv testing transformer has 8% leakage reactance and resistance on 100 KVA base . A cable has to be tested at 500 kv using the above transformer as a resonant transformer at 50 hz . if the charging current of the cable at 500 kv is 0.4 A find the series inductance required . Assume 2% resistance for the inductor to be used and the connecting leads . Neglect dielectric loss of hte cable . what will be the input voltage to the transformer ?
Explain the terms real power, apparent power and reactive power for ac circuits and also the units used.
WHAT IS THE FAULT WHEN 100HP TURBINE MOTOR TRIPS, LIST THE FAULTS AND ITS TRABULESHOOTING TIPS.. MY AUTO TARNSFORMER STARTER TRIPS
What is main cause of cable's terminal point burned in Lug on high temperature although lug and cable selection is ok as per stantard and also tightness is ok as per situation. so please take in deep and tell correct answer thanku.
if you are in a software company,then why do you want to come in a core company like sail, ntpc(where lots of trouble like tension but you have a good life in a it company) ?
What will happen if the d.c. Shunt motor opened accidentally running on no-load has its shunt field winding?
if sf6 gas low in gis what will happen
Why neutral point is consider as zero potential?
what's the difference between 'shaft power demand' and 'BHP' , when we consider electrical load list.
Sir,In our company there are 3 caterpillar make(capacity:(1) 3.3KV,2.5MW(2)3.3KV,2.5MW & (3)3.3KV,1.9MW) & 1 deutz make (capacity:11KV,3.8MW)gas engines utilised,all are running in paralell. There are three transformer utilised,(1) 6.25MVA,3.3KV/22KV,Impedence voltage:6.7% used for two generator,both are 2.5MW(2)5.5MVA,3.3KV/22KV,Impedence voltage:7.2% used for one generator of 2.5MW & (3) 5.5MVA,11KV/22KV,Impedence voltage:7.8% used for one generator of 2.5MW.all generator breakers capacity of 1250Amps. Sir,I want the details of fault level calculation of generator,transformer individually & for whole system. If you require any information from me.feel free for contact me sir.pl.send the answer of my question as the earliest as possible.
which motor have relatively high power factor and what is reason for have high pf? 1.capacitor run motor 2.shaded pole motor 3.capacitor start motor 4.split phase motor
WHY EARTHING NOT NEEDED IN BATTERY IN SUBSTATION
In Dyn11 power transformer if any one of the 3 phases connected to earth in star connected side then please explain effect of the current flow in delta connected side of transformer.(In this case if one phase is shorted to ground in star connected side then we observe the current flow in two phases only not three phases in delta connected primary side. Please explain why it is so?)
For overhead protection we use which transformer?