what is the procedure for three phase motor differential
relay testing
can it do with single phase test kit?
Answer Posted / santosh kawade
Three phase motor differential relay testing can be done
with single phase test kit.
There are two type of relay testings:
1) Primary injection : In this testing entire system
(including relay, control wiring and power wiring get
checked),
2) Secondary injection : In this testing generally we check
relay only.
By using single phase test kit:
1) Primary injection :
a) Carryout shorting of all three phases of motor winding
by using short link for individual phases seperately.
b) Inject current by using current injection device (for
inzone and outzone fault)
3) Check stability of relay for outzone fault and operation
of relay for inzone fault.
2) Secondary injection :
Directly inject fault current in relay terminal and check
proper operation of relay.
Santosh Kawade
9224 69 3116
Is This Answer Correct ? | 6 Yes | 2 No |
Post New Answer View All Answers
at meter room 50 hrc switch installed,but there are not get earthing proper,so what happen?and 11kv transformer out put going in to hrc main 400a three nog each? so earthing is require for all switch? (some customer made earthing at there home.)
sir please send me iocl written test paper in my e-mail account. i'll be obliged to you........ thank u roshan
why is control bus bi-directional?
As per standard, transformer body earthing and other Equipment earthing (Equipment earthing) did not connect. but in LT side termination we are doing metal glanding in both side Transformer to PCC Panel through armoured cable, now X'mer body earthing and PCC Pane earthing (Equipment earthing) both are connect.is this safe for X'mer or other equipment?
howmany electrician should maintain for a 1000 kva used plant... in kerala..
How to protect sensitive loads such as Dosing pumps inside a factory from voltage surge/voltage fluctuation.
Explain different types of d.c motors? Give their applications
how could we know the size of cable by physical view?
i ha done my 10th with 71% ,ITI with 81% 11th with 75% 12th 43% apprentiship with 71% in SAT i secure 1390 ,TOEFL 27 i was refused four times and in all me interview visa officar told that i am not Qualify for study in USA but i completed my 12th yes i got low persentage in my 12th but i seen to much student they already got visa with them 3 or 4 backlocs so why they are refused me ?
HOW CAN YOU CALCULATE PRACTICAL EFFICIENCY OF A ASYNCHRONOUS INDUCTIONMOTOR OF 7.5KW,& MOTOR IS RUNNING WITH AVOLTAGE OF 410 VOLTS,& TAKING CURENT OF 13 AMPS
what is induction furnance? how many phase supply given io its coil for 15 or 20 ton furnance?
How the circuit breaker is selected for Induction motor of 100 kW, 415 volt, 0.85 power factor, 0.95 efficiency ?
what is mathed of check the D.C MOTOR 181 KW (ARMATURE AND FIELD) WHAT IS THE MATHED OF CHECK THE THYRISTOR MODULE (HIGH CURRENT)
what is the difference between the characteristics of two different phase bushing of any transformer
how to calculate voltage drop and followed by cable calculation?is there avail in formula?