after parallaing two generators current is shooting up in
both the generators.for ex: load is 400 kw..after paralling
and load sharing current in running gen is approx 900 amps
and incoming is 750 amps which is too high when trying
toshift the load current in incoming gen is coming more
than 1300 amps and both getting tripped and making
blackout..
Answer Posted / pillay
it looks like one of the genset is having a big difference in voltage or
the droop kit if fitted something wrong with it or
check after paralling do you have balanced three phase voltage and current or one of the phase is open circuit or
the gen is running the other as motor
if you know the actual reasons later please let us know also
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
why the making current is more than then the breaking current and if its true then its about a controling circuit or breaker power contact points
List examples of current sources?
which of the following elements is not present in stainless steel
Details about Flux Compensated magnetic Amplifer starter for motors
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?
what are the interview question asked in wind mill about electrical
what is formula to cal cute earth pit numbers and size of earth strip used in earthing?
what heppend if we are connected u1-v1-w1 as a star point in the place of u2-v2-w2 in power genration
What is the use of iron core in a transformer?
Define closed loop control system.
How to calculate cable size in HT AND LT
In between UPS out going changer over switch and ups raising main input, both side cable gland producing heat but the cable doesn't get heat,Why?
what are the disadvantages in GIS over AIS
why does rotor rotets?
Dear all, how we select the cable size according to current with or without including different correction factor , is there any direct method for sizing of cable...