how to choose the cable rating for load (KW)? EXAMPLE.50KW load
Answer Posted / engineer
Right cable size Sellection depends on 3 factors:
1- Load Current.current(I) = 50kW /(1.732*415*0.85
(p.f)) =139A
2- Distance(From feeder to your load)
3- Allawable Voltage droop in your system (Should be less
than 5% )
As experience you can use 10sqrmm for 40A,for 120meter.
Is This Answer Correct ? | 117 Yes | 52 No |
Post New Answer View All Answers
What is the criteria that generally follow by distribution licenses to fix contact demand of their industrial customers?
why r we using shell transformer for low voltage
how to Select its CORE in electrical cables based on its applications? or Application of various types of electrical cable based on it CORE?
What is PEC??Applications........
how to check regenerative load in drived motor
what will happen if frequency is below 50 hz?
How can I calculate per unit (KWH) fuel (Gas/ Diesel both) consumption 1MW unit?
i need to now what will be the cable size to the following load, transformer to distribution panel distance 110m, load 1000kw, voltage 400v, pf 0.85, permissible voltage drop 2.0%, overhead line, atmospheric temperature 35 degree c.
sir, 3phase induction motor takes different pf and different KW in three phase while running,explain reason
what is meant by surge? what we called for high currents?
To prove the capacity of a 10MVA transforemr with 6.5% impedance by a short circuit test how much power is needed to inject an impedance voltage if we have to arrive for its rated current?
Why ground terminal is used in pot meter 10k ohms
Why Water motor is not taking a load or pressure while everything is correct. (Note: Motor running properly)
how to calculate cable size in diffrent loads?
what is meant by flywheel and its role in retardation test