Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What will be the total current for 300kva UPS if it runs on
40 to 45 percent load. Is there any formula for to
calculate the exact load.

Answer Posted / thowsif_emerson_csm team

For 300 KVA the Full load Current=KVA*PF,
i.e 300x.8=240000 Watts.

we know in 3 Phase Circuits,

P=1.732x V x I x Pf,

I=P/1.732xV x Pf,

I=240000/1.732 X 440 X 0.8,

Full Load Current, I =240000/609=394 Amps,

The Load Current @ 40% is 394*.40=158 A(Total Load Current).

The Load Current @ 45% is 394*.45=177 A(Total Load Current).


So load current at 40% Load is 39*.40=15.6 A/Phase Amps.

Is This Answer Correct ?    11 Yes 6 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what do you mean by plant earthing system.

2080


how to design coil turns ?

1992


what is cogging and crawling

2555


how we can explain arc heatng?

1952


how can I calculate charging current of cable/overhead conductor? what is roll of voltage in it ?

3688


why do we use spark detector inside the slip ring brush compartment 0ona slip ring induction motor?

2106


I have motor of 3 H.P. How i found the rating of capacitor use in it in single phase motor..???

2646


IN dc capacitive reactance is??

1407


We have drive feeding an output contactor for a 5000 hp motor @ 5kV application. The motor FLA is 629amps x 1.25% service factor = 786.25 amps The cable that we current have in place between the drive and the output contactor is 350kcmil- MV-105 (parallel cables). Per the NEC table 310.60 (C) (69). This show the cable ampacity is at 615 amps per cable for a rating of 1230 amps. We have derated the cable for the cable tray and the multiple cables application and our calculations show that after the correction factor factor we are at 922amps. 1230 amps x .75% correction factor factor = 922.5 amps. The customer is driving us to then use another safety factor of .25% off of the already derated cable. Can you please provide a longhand calculation for your solution on this application?

2154


What are the differences between single phase and three phase?

2055


What is servo motor and what are different types of servo motor

2404


1.why should we connect the measuring instruments in l.v side in short circuit test of a transformer? 2.why the power factor is less in open circuit test of a transformer?

2082


how to calculate percentage impedence at 75 deg C at normal tap

2271


whate is the meaning of balance/unbalance,in stabilizers type

2140


In a large office how do we calculate required number of light fittings, assuming fittings are 4x18W or 2x36W fluorescent fitting ?

1885