We have 2 no. 4MW DG set. and GEB supply.
But, we running, only 1 DG set. when we done APFC/Power
factor setting : 0.90, then winding temp. Low. but when
setting done : 0.83, then Winding temp. increase.
WHY Why ? ? ?, plz give me answer.
Answer Posted / gurucharan singh
this is clear that at lower pf settings, its the DG which
compensate for the KVAR. which results in the high winding
temperature. For this check the plant loads connected. And
KVAR supplied by EB & DG. Also during parallel with grid DG
generally act as KVAR compensator along with KW supplied.
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
What happens if the Capacitive Voltage Transformer Primary neutral is not earthed. There is a CVT between Transformer and source, and the CVT neutral of the transformer is not earthed, does it effect the transformer while charging or does it effect the transformer charging process.
Why are the cores of large transformers built up of circular transactions ?
WHAT IS THE MEANING OG (li = 7 In)
can you plz send l&t aptitude questions if available its urgent plz plz plz
We have Diesel generator of 200KW. fuel consumption is always same,even connected light load or full load. Is it right?
Why auxiliary transformers are not connected in parallel in primary stations?
Which is the largest hydropower station in the world?
how does the rotating m.m.f is produced in the 3-phase induction motor and how the poles are created in 3-phase induction motor ?
can we choose current transformer secondary, to calculate residual flux in a power transformer, so as its saturation is close to the saturation level of power transformer?
Explain about c.t?
diameter of cable and core is doubled then the value of capacitance is
How can we find out LT UG cable fault (size,from-4*25mm sqr to 4*300mm sqr)? How mani types UG cable faults?
What is domestic transformer? Draw the connection of domestic transformer.
Pls Breifly explain about UPS (Inverter,Reserve,Rectifier,Float voltage,Boost voltage).
1600 KVA ka transformer hi aghar lt side par 800A aur voltage 420 ho to HT side ki cable ki rating keya ho gi?