Answer Posted / y.rama krishna
Connect 1U&2U
Apply 3ph 415V balanced voltage across terminals 1U,1V,1W
(HV wdg)
Measure the voltages between the given terminals & record
1)1U-1V
2)1V-1W
3)1W-1V
4)1V-2V
5)1V-2W
6)1W-2V
7)1W-2W
8)1U-2N
9)1V-2N
Verify the conditions
a)1W-2W = 1W-2V
b)1V-2W = 1V-2V
c)1U-1V = (1U-2N)+(1V-2N)
vector group Dyn1 confirmed if the above conditions are
satisfied.
Is This Answer Correct ? | 18 Yes | 16 No |
Post New Answer View All Answers
What descriptive information does the NEC require to be marked on all conductors?
At full load wat is the motor p.f And at no load will is the motor p.f?
Form S and "c" license application both are same? @ tneb portal
What is the de rating factor of cable? What is the importance of the de rating factor in cable select
What is the difference between a fuse and a breaker?
hi friends how 3 phase converter functioning ?what is working principle of rotory phase converter ?
how to calculate single phase motor efficiency ?
How will polarity test of Dy5 Transformer ?
What should be the voltage between Neutral and Ground in secondary side of the step down transformer (230 V to 110 V) with no load condition?
we have two generators different capacity on 15 MW and other 6MW at 11 KV , 15 MW gen. bus short level current 40KA,and 6MW short level current 25KA,, length of cable 100MTR between 6 MW from 15MW gen. for bus coupling . kindly tell any one can we use both NGR OR one NGR from any GEN. BOTH NGR has diff. rating. Tariq pakistan
What is expention fastener (Fan)
Draw the line diagram of diffretial relay connected to transformer?
What are the major reasons for balancing hydro-thermal mix?
is it true there's a big difference in using Cummins or Denyo...especially power output or leakage
What is the formula to calculate the no load current of a single & three phase induction motor