A three phase load, around 4 km away from the 11/0.433KV
distribution transformer (Neutral of Transformer is
solidily earthed) and consisting of mainly very costly and
sensitive electronic equipments is giving trouble due to
high voltage difference between neutral and body earth.
Whether this problem can addressed by connecting neutral at
the load point solidly to earth?

Answer Posted / parul

Check the load circuit properly.Check the transformer at
open and short circuits.Isolate the neutral earthing in the
substation transformer and check the voltage in all phases
to find out whether transformer is the problem or your load.

After considering all above checks you may do the earthing
of neutral point in your load.

Is This Answer Correct ?    1 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

draw vector diagram and +ve,zero sequence diagram of symmetrical three phase fault.

1495


What is the difference between isolators and electrical circuit breakers?

631


How does PLC work for sychronising of Two or more DG sets?

1646


How to setting the volume of RTCC panel AVR (11kv) controller

1183


How to know vacuum in vacuum cylinder of breaker in working condition

1509






how much cable size required for 70 kilowatt load.

1157


Why magnetic flux produces an induced current?? what is the detailed procedure ?? ans plz

3252


What is control system?

734


What are two contours of nichols chart?

628


Can we transmit digital signal to long distance ?

1486


We have a distribution transformer of 750KVA/11kv/440v and an AVR (Servo Stabilizer) of 750KVA on the LT side of distribution transformer. Also we have an ACB of 1200A on the output of distribution transformer (that is on the input of AVR). We want to have an MCCB on the output of AVR. What should be the rating?

1641


How to calculate Air conditioning capacity for a telecom BTS shelter?

3048


why we are using Load factor?

1370


There is air in a room . the top and bottom of the room are at constant temp. T1 and T2. DRAW THE temp profiles if a. T1 greater than T2 b. T1 less than T2

1434


If one tertiary phase i.e. R,Y or B is earthed of a loaded type tertiary delta connected (Without load)of a power auto transformer, what is its advantage/disadvantage?

1617