Answer Posted / khalid hussain shaikh
POWER=1.732*VOLTAGE*CURRENT*POWER FACTOR
HERE POWER=2500KVA
VOLTAGE=11 KV
POWER FACOR AS STANDARD=0.85
I=?
I=2500KVA/1.732*11KV*0.85
KV CANCELLED EACH DENOMINATOR AND NUMARATOR,
I=2500/1.732*11*0.85
I=154 AMP (11 KV SIDE)
I=2500 KVA/1.732*415 V*0.85
V CANCELLED EACH DENOMINATOR AND NUMARATOR
I=2500 K/610.963
I=4.091 KA
I=4091 AMP
| Is This Answer Correct ? | 10 Yes | 16 No |
Post New Answer View All Answers
Can Anyone suggest the Standards (IEC or IS) for selecting copper current density?
What are the main advantages of generalized error co-efficients?
why all the feeders are designed in a particular manner ... is there any reason for that???
How much inductance or resistance require as a starter in series with induction motor of specific capacity(e.g. 5 hp) ? What is formula for it ?
what type questions asked in hp cl
HOW TO CALCULATE THE REGULATION OF 100 AND 25 KVA TRANSFORMER
what r substations?what r there work?why voltages r incresed and then reduced during distribution of power
What is the difference between cylindrical-type and sandwich-type winding?
v/f drive basic princeple
Y phase plates are used in transmission line??? what is there need???
How to choose the vector group for the step up and step down transformers??? Tell me the which vector group is suitable for step up and step down transformers and whats the reason to choose and whats the benefits???
What is the drawback of class b amplifier? How is this minimized?
If a 3 phase induction motor is in off condition in the conveyor and rotor of the motor keeps moving with the conveyor than the resistance of windings of motor varies. why is it so ??
what is draiv work
any earth foult trip the relay but in welding time not trip by earth foult