What would be the ratio of a Delta-Wye tranformer having
48000 volts phase to phase on the primary and 4160 volts
phase to phase on the secondary?

Answer Posted / nain

voltage for delta side will b measured line voltage(phase
to phase)
voltage for star side will b measured phase voltage(phase
to neutral)
as u hav given both line voltages so for star side v will
convert that to phase voltge i.e.4160/1.73=2404.62

so ratio=48000/2404.62=19.96

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

can i use 2000/5A Clamp meter to measure HT cable

1563


how to determine the cable size...pls explain me with the formula taking particular load....does the factors like impedance & short circuit rating influence the cable size, if so how....

1581


Define noise?

715


Who are the manufactures those manufacturing 3Cx2.5sqmm FRLS cables. I heard about FRLS technology adopted only in wires useful for wirings

1626


Best way to measure the Soil resistance of rocky soil, three probe method and four probe method

1455






Sir 33kva 2 transformer load 900 amp calc 1800 amp mana jayega

1365


a 100mva,400/200v transformer has leakage impdce of 10% draws a steady state line currentof---------------

1461


what is the main difference between power devices and signal devices

1691


why using transformer and thyristor switch in 3 phase apfc panel

2378


How many Zones can be in Conventional type fire alarm system & how can we detect the fire in Conv. type FAS?

1377


what is a vector protection in transformer

1522


how slip power recovery system work

2532


Why do we perform an open-circuit test and short-circuit test on the transformer?

632


How much weight an electrical engine can pull??

1623


EXPLAIN WHY THE SURGE CURRENT RATING OF AN MCCB OR CIRCUIT BREAKER DECREASES WITH INCREASE IN THE RATING OF MCCB OR CIRCUIT BREAKER.

1531