how we can calculate which capacity capacitor bank we have
to add for improve pf?

Answer Posted / z_hosen

More simply,
Let total power is 1500kw

assume
cos 1 =power factor before improvement =0.75
cos 2= poer factor after improvement =0.98
tan1=0.88
tan2=0.2
and
kvar 1= power*tan1=1500*0.88=1320kvar
kvar 2=power*tan2=1500*0.2=300kvar

now, required rating of capacitor bank =kvar1-kvar2
=1320-300
=1020kvar =1000kvar

thanking u
z_hosen@yahoo.com

Is This Answer Correct ?    11 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the maximum percentage voltage drop (vd%)for a motor control center

1545


3 phase Motor will be given 2 phase after 2 to 5 second we given 3rd phase so Motor Run sum-time in forward or sum time run reverse direction. All time phase sequence is not change. Why motor run in reverse direction? Please Explain........

1483


I have a small system with two motors that are running on 380 vac, 60 hz. These motors are expensive and I usally get them from Brazil. I am adding another motor to the system, but I want to purchase a 480 vac, 60 hz motor to use. It will be on a VFD that is rated fro 380 thru 480. Is this posible and will I have to use a larger motor and derate it?

1528


I need to connect a synchronous generator to the grid using automatic synchronization and two circuit breakers (one for synchronization, one for end connection to the grid), how to determinate the required diameter of the cables?

2051


In single phase ac ups supply when current is measured with tong tester neutral current is found more than phase current.What is the reason?

1604






Single line diagram for dbb (double bus bar)system.

1468


What is ferro-resonance in electrical system? Why it occurs and what are measures to prevent it?

1762


while doing high potential for 11KV 3 core cable how much leakage current will obtain?, what will be acceptance value?

2427


how much flux density of CRNO core

2335


In a flange coupling, the flange bolts are designed for

700


Explain bypass capacitor?

648


what is mean by Digital Logic Meter (DLM)

1861


What descriptive information does the NEC require to be marked on all conductors?

1461


On a 6 KVA UPS we have to provide a DC MCB for Battery bank of 16 nos (12 V 42 AH). What Shall be the current rating of DC MCB ?

2117


why impudance relay used for medium transmission power system? why not others?

916