If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / sukhvinder
connected load=375kw
kva=kw/cos phi
kva=375kw/.8
=468.75
extra load= 20% (assume) i.e 468*20%= 93.6
total 468.75+93.6=543.68 kva say 550kva
eff. 375/550*pf (0.8)*100=85%.
| Is This Answer Correct ? | 25 Yes | 2 No |
Post New Answer View All Answers
Pl. brief about break-down maintenance of machine tool.
how can we save enegry by using VFD for Resiprocating Air compressor which is having more unloading running hours
The Howland current source produces a A Unidirectional floating load current B Bidirectional single-ended load current C Unidirectional single-ended load current D Bidirectional floating load current
how the CT and PT is connected in the circuit during testing of transformer explain with diagram
armature winding of dc machine produce alternating emf then it convert in to dc by using commutator.But only we consider armature resistance why don't we consider inductive reactane effect?
What is control system?
what parameters should we check to reduce the power bill
what is working process of star delta controlling circuit ?
Difference between on line capacitor and Station type capacitor
1. A bomber drops a bomb from an aircraft flying at 2000 km/hr. at an altitude of 7km. The speed at which the bomb will strike the earth would be
What is “pu” in ee?
While testing a ZCT what parameters have to check or measure?
In the formula : Knee point voltage = Burden X alf / class, Please inform what is alf? regards Shashidhar M.R.
What should be the voltage between Neutral and Ground in secondary side of the step down transformer (230 V to 110 V) with no load condition?
What are gain margin and phase margin?