If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / sukhvinder
connected load=375kw
kva=kw/cos phi
kva=375kw/.8
=468.75
extra load= 20% (assume) i.e 468*20%= 93.6
total 468.75+93.6=543.68 kva say 550kva
eff. 375/550*pf (0.8)*100=85%.
Is This Answer Correct ? | 25 Yes | 2 No |
Post New Answer View All Answers
HELLO SIR, IAM PREPARING HPCL EXAMS. SO PLS SEND MATERIAL OF HPCL ELECTRICAL ENG..TO VIJAY_8888@YMAIL.COM
what is the AC Plant and how can do the work with parts and picture tell us 150 Tr
For R-L or R-C ckt,time constant formula is L/R and RC respectively and its unit is in sec.Pls tell me the derivation
with 3 phase board on a 63 amp rcd is it ok to have 6 electrical showers 2 on each phase and what problems could happen
For small size, high frequency coils, the most common core material is- a. )Air b. )Ferrite c.) Powdered ion d.) Steel
what is physical distance of isolator to VCB in 33/11kv sub stations
how to generator maintenance (A Check, B check,Etc)
Why do we need a separate control desk & PLC control panel in Boiler plant or coal handling plant? Can we provide cost effective Control desk cum PLC panel. Is there is an specific need for control desk.. kindly advice.
Suppose a 3 phase, 2 pole, 440V induction motor is driving a flywheel of 600mm diameter, 150kg mass. By using v-belt and pulley, the speed is increased to 4500 RPM. What will be the effect on motor current?
kVA rating of ordinary transformer is increased when connected as an auto transformer because A transformation ratio increased B secondary voltage increased C energy is transferred both inductively and conductively D secondary current increased
What is the abbreviation of NGT panel
what are the range of memory address in plc for L&T lx7 4A
hi there i am highly enthusiastic about discussing electrical concepts , and hence i wud lyk to invit al do intrested to join me at gtalk and hav a dscussun of the concepts , ad me as a freind . my email id is rakesh.2k99@gmail.com
How to know about the rating(voltage and other) of induction motor if its name plate is missing at the manufacturing site.
1.what is the reason for transformer and lightning arrester blast in 33kv system