What will be the total current for 300kva UPS if it runs on
40 to 45 percent load. Is there any formula for to
calculate the exact load.
Answer Posted / pratheesh
We can calculate the total output current of a 300kva ups.
P=√3*V*I*CosΦ
Where P= Output power of UPS here 300000VA
V= Output voltage of UPS ( I hope this is a 3 phase
415 volts UPS)
I= Output current. (We need to calculate)
CosΦ= Powerfactor of the load. Varies depends the
nature of load(Inductive, Resistive or
Capacitive. We can assume this value is as 1
because we dont know the powerfactor, nature of
load.
So I= P/(√3*V*CosΦ)
= 300000/(1.73*415*1)=Approximately 420A per phase(if
the load distribution is balanced on each phase)
So, If the UPS runs on 40 to 45 percent load, it will take
around 170 to 190 Amps on each phase.
Is This Answer Correct ? | 14 Yes | 8 No |
Post New Answer View All Answers
what are the effects when a salient pole alternator is run at high speed like 3000 r.p.m?
The power supplied to a 50mH inductor from a 120V, 60Hz source will be
Why we are using only Dyn11 tranformer in distribution system but not using a Dyn1 in distributing system?why not and advantage and disadvantage in both
Which level of the Transformer oil got dielectric strengh? And why?
I am apply the AAI. So i want electrical sample question paper in technical with answer my id is vijayjobsmart@gmail.com
there is an alternator 480 k.w, 400v,50hz, 4-wire running on load having leakage alternator body earthed current 38 A. is it within acceptable limit? if yes then give reference if no then how to bring within specified limit
how to apply b license to c license in tneb
what is the meaning of the symbol << >> put in transformer drawing
WHAT IS MOBILE SUB-STATION? & REALLY BENEFIT IN INDIA
How to size fuse? How to size MCB?
we are having 15kw and 3kw motor both can run in same time , instead of using copper we are using ug aluminium cable , 35 sq.mm is suitable for its current carrying capacity..?
electromechanical relay type identification example : type=tjmh t-stants for j- m- h-
state the working principle of incondenscent tube?
how to calculate kvar in Akiva
Whether the vacuum contactor requires Short circuit protection?If No,why?