I have installed capacitor bank at secondary transformer.
cos phi is increase. but on load (far from transormer), it
still poor. Can anybody explain it??
Answer Posted / heamkumar
Capacitor Bank is used to improve the Power Factor.
As you said, Pf will increase only in the incomer side.
Because you have connected the capacitor bank in the
secondary side near the incomer. So if you need to improve
the pf near load, you need to place the capacitor bank near
the load, but according to the load. So if you put the
capapcitor banks near the load side, power factor will
improve not only in the load side, but also in the incomer
side.
Is This Answer Correct ? | 11 Yes | 0 No |
Post New Answer View All Answers
If a air condition consume 2.50 to 3.00 amp then how much it will consume in watts if it is running 10 hours out of 24 hours????
pls tell me function of closing coil of A.C.B.
what are the condition that makes hooter blow?
Briefing the effects of ASR and ACR of a double closed-loop speed regulating system.
How we can calculate the consumption in kwh of motor on basis of kw @100% load, @50% load & @ no load.
What is systematic error?
plz send me the placement interview question and answers of whizchip(technical and apttitude)..i have an interview in next.
ho can we calculate the conductor insulation value according to their ratings like voltage,current etc.how insulation value related with voltage,current and power of amachine
how to test and calculat the head and discharge in borewell compressor
how did i get the competency certificate as electricle supervisor. iam completed my b.tech.but i dnt have any experince, this certificate is required for applyng ongc mangement trainees. what should i do sir please suggested me
why d.c produces corrosion
What are the uses of lead compensator?
how to calculate the power factor when instantaneous voltage and current has harmonics in it ?
What is the relationship between voltage,current & frequency?
Mention the methods for starting an induction motor?