Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

if 50hz transformer is required to be run on 50% frequency
what needs to be done???????????

Answer Posted / pankaj rajput

It will trip on over fluxing protection, if the protection
is installed.

It's not a wise situation to connect transformer to a lower
frequency with same voltage. The flux induced in core is
directly proportional to voltage & inversly proportional to
frequency. Hence the core will be over heated/over fluxed
and may get damage due to over heat.

The only remedy is reducing the voltage in same ratio.

Is This Answer Correct ?    31 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

upto how many load can v connect to stabilizer which is used for tv

2237


why only exciting current is shown not primary current in transformer???

1869


what is vtg limit of earth and neutral at transformer side?

2035


Single line diagram for dbb (double bus bar)system.

1942


State the methods of improving power factor?

1146


What is the power factor of an alternator at no load?

1336


An impedance of 100 ohms resistance and an unknown inductance is connected across the capacitor. The resulting impedance is a pure resistance of 500 ohms ifω = 10^5 rad/sec. calculate the values of inductor and capacitor.

1419


What are the main advantages of bode plot?

1253


How to test REF relay testing for LV panel as per Kahramaa standard?

4937


Anyone who can recommend an equivalent to Envirotemp FR3 of Cooper?

1960


i have install 750 kva distribution transformer at my site and want to do neutral earthing. what calculations should i follow to determine earthing conductor material and size?

2060


what are the differant std sizes of cable trenches?

2051


Why hydropower stations are preferred solution for meeting peak loads in grids?

1003


How to setting the volume of RTCC panel AVR (11kv) controller

1593


why swityard is necessrry requirement in any bis power distributin systems?

2374