three phase 180kva diesel generator can take how much load
in amp and what is formula to get this?
Answer Posted / gins
Now a days DG manufactures assuring that the DGs can be
loaded up to 120% of its rated capacity. But it is always
good to design DG for a maximum load of 80% of the rated
capacity to get the maximum efficient running. In your case
You can load a maximum load of 125.8 kW at pf 0.85. So you
have to give an incomer of MCCB with rating suitable for
125.8kW.
W=root3 x VI x pf
so I = W/root3 x V x pf
I think 250A, 16kA, 4Pole MCCB with 80% plug setting may be
suitable for you.
Accordingly select your incomer with suitable kA rating
with respect to your total load.
| Is This Answer Correct ? | 20 Yes | 5 No |
Post New Answer View All Answers
I want definition for ABT Meter (Availability Based tariff) ?
what is the prosses for getting of 33kv licence (i have completed my engineering degree & working in 33kv substation for contract basis )????
What is VSCF windelectrical system?
what precautions to be taken while desigining a LT,HT panel. Eg-LT panel PCC panel with ACB installed. HT panel VCB panel with VCB installed. & what is main diffrence betwn IP54 & IP55 construction of panel.
How is magnetic leakage reduced?
What is the difference between cylindrical-type and sandwich-type winding?
what are the main faults that occur in stabilizers? How they corrected and resolved ? Types of stabilizers ?
what is the mechanism of operation of brushless dc motor why is it more wexpensive then ordinary permanent magnet motors
In hydel power plants, L.A's, S.C's are placed inside the control panel boards. what is the purpose? [already the total body was earthed to ground.]
What are the types of piano switches?
11kv/433v delta/star distribution transformer primary side full load Ht current is 83.33A in , but input side VCB rating 800A.why?
What is deference between MCB & MCCB & ISOLATOR
How you calculate the repturing capacity of a HRC fuse
I am having a 1500 KVA transformer whose secondary current is 2086A and my connected load is 1000 KVA, I am having 400 KVAR APFCR for PF improvement what ratio of CT should i install in LT EB Bus to get optimum PF improvement?
define the active power?