What the capacitor Current formula?, For 1 KVAr how amps
its required? for using the KVAr for boosting the PF Design
Calculation.( Eg: for 30 KVAr required how many KW?)
Answer Posted / mehmud ahmed
Hi every one how are you
if u need to know three phase capacitor rating than
I= kvar x 1000 / V x 1.73
Example:
i have 25 Kvar capacitor and line to line voltage is 440. i want to know current rating of capacitor
I = KVAR x 1000 / V x 1.73
I = 25 x 1000 / 440 x 1.73
I = 25000 / 762.08
I = 32.80 Amp
So my Ans is (32.80 Amp)
| Is This Answer Correct ? | 70 Yes | 4 No |
Post New Answer View All Answers
What is your acheivements
What are the three major categories of error?
Safety of dry type transformer
whatare the disadvantages occur,if the form factor of transmission will not be equal to 1.11
How much kv gas generator is needed to run 2 hp and 1 hp airconditioners, plus a refrigerator and 4 Tvs
why is a power transformer used only occasionally?it is used to step up at generating stations?and that needs to be done all day long !!!!!!!
Define pole pitch?
Which motor is 3.3 or 11kV more reliable, in terms of efficeancy,maintenance, reliability.
We are planning to synchronized DG's with our captive plant in the event of black start of plant, but before sync we checked voltage of DG with our plant voltage and it varies from 5 V to 450 V. So in this condition how we can sync DG with plant ?
What descriptive information does the NEC require to be marked on all conductors?
An ISP is granted a block of addresses starting with 150.80.0.0/16. The ISP wants to distribute these blocks to 2600 customers as follows. a) 200 medium size businesses; each needs 16 addresses b) 400 small businesses; each needs 8 addresses c) 2000 households; each needs 4 addresses Design the subblocks and give the slash notation for each subblock. Find out how many addresses are still available after these allocations.
is it value of power factor is more than unit. whats effects in the source supply
If 100 KAV USP dedicated earth got disconnect / Cut. What will happen at load.
how much leakage current is allowed in MC61A L&T make relay?
If we impress a dc voltage of 230 V on an unloaded 230 V, 50 Hz transformer it wi A give high secondary voltage B burn out C give secondary voltage as per K D none of these