if field commnictor 475 does not communicate with transmitter
what will you do ?
Answer Posted / abu maryam
In my opinion there are several causes of this problem:
1- Check the power source if it 24 volt or not.
You should disassemble the power source if it is 24 on out side and still 24 after connecting to device this mean that the power source is good but if it is 24 volt out side and zero after connecting this mean there is found problem in power source (may be problem in module).
2-Read device data if it support hart protocol or not.
3-Disassembled device and connect separate power source and connect 250 ohm series if it no benefit added change the resistance from 250 to 1000 ohm and try or disassemble the resistance and power source and apply power source from multi function calibrator which has internal resistance then try to connect.
4-May be device support hart but hart property is disabled by definite internal jumper in device so we should change this jumper according to device manual.
5-May the device support hart its data files is not added to hart communicator for 1 of the following 2 reasons:
the first:hart communicator is not updated.
The second:the device data filed is not added to hart communicator and it need its special programs and its special cable as found in foxporo transmitters.
6-May the connectors or cables has problem so use another cable.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
please any body have most important data for study for saudi aramco test of instrument QC thanks email shahnaveedullah@gmail.com
selection of the zener barrier for the hazardeous area zone 0
need instrumentation job completed 1 year trainee ship in mnc pesticide company. now in search of job
If we increase only P what will be controller action ?
What is Predictive Maintenance
can any one tell me when ongc placement test and its forms is available????/ pls tell me if u know
Calculate the maximum pressure drop that can be allowed to occur across a control valve, so that we can prevent cavitation / flashing from occurring. Use the following formula: Δ P allow = Km (P1 – PvapourA) where, Δ P allow - the maximum allowable differential pressure for sizing purposes, or terminal pressure drop; Km- the valve recovery coefficient from the manufacturer’s catalogue; P1 - absolute inlet fluid pressure; PvapourA - absolute fluid vapour pressure at the inlet temperature; Use Atmospheric pressure = 101.3 kPa, P1 = 1200 kPa(g), PvapourA = 4 kPa, KM = 0.72
What happen if I install my pressure transmitter below the elevation of pipe in natural gas service?
Draw a wheatstone bridge circuit showing supply, meter and 3 wire RTD connection
how can i check vortex shedder bar it is ok? if there is ohms condition are shown correct?
Drum level tx with GP4 with zero elevation:7300mmh20 on HP and 8050mmh2o on LP as range but on commissioning the tx readiing is max,Why this reading?
how u calibrate pneumatic n motorized c/v?
What is the Working principle of Dozing valve?
hi sir yhis is zahid ali i am preparing for the jspl at oct.4.please send me the recently updated sample paper.
Speedtronic system .