During the main stator winding insulation testing (phase to ground)of 11kv alternator (Lerysomer) i found 0 and resistance with multimeter and found 20 killo ohm while the power cables are connected both end (Generator & VCB). In VCB PT (Potential transformer) are connected.
Please any body explain that method of insulation is correct or not? also describe of PT connections
Answer Posted / k.prakashchandra
Supposing that you have disconnected the neutral of GEN , you will measure the dc resistance of PT as the other end of it is earthed . 20 K ohm will be measured as 0 M ohm by the megger . If you want to test insulation of GEN , you have to isolate the winding from everything .
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
what about GD square and its important for motor design?
what is the excess air in furnace
Why Water motor is not taking a load or pressure while everything is correct. (Note: Motor running properly)
What is meant by analogous system?
If oil and air can withstand a high MeV when used as an insulator in a transformer, what are the values of how high for each material?
how load of a turbo generator can be increased
How To increase Knowledge Of boliler regarding To Only Electrical Field..
what are the basic insulation levels & what its Unit
What is time invariant system?
control & auxilary circuits used for circuir breakers
If only R Phase is connected in 2 pole elcb, n is not connected than it will work or not in ground fault.
How to know any size of cable if there are not written on cable? Answer must be theurical not by experience.
what percent do you derate your copper wire when you change from copper buss to copper wire
I am shobana from Chennai. I am having my personal interview on 19th Dec at Chennai.kindly mail me the questions to mail id shobana.shanthi@gmail.com
How to calculate Temp from Resister from PT100 equation,