Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

During the main stator winding insulation testing (phase to ground)of 11kv alternator (Lerysomer) i found 0 and resistance with multimeter and found 20 killo ohm while the power cables are connected both end (Generator & VCB). In VCB PT (Potential transformer) are connected.
Please any body explain that method of insulation is correct or not? also describe of PT connections

Answer Posted / k.prakashchandra

Supposing that you have disconnected the neutral of GEN , you will measure the dc resistance of PT as the other end of it is earthed . 20 K ohm will be measured as 0 M ohm by the megger . If you want to test insulation of GEN , you have to isolate the winding from everything .

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

In cable sizing calculation (determining the max route length of cable) why we choose the shortest length between cable length of full load current Iflc & starting current Istart?

3304


What is the formula to calculate a three phase alternator

2320


howmany electrician should maintain for a 1000 kva used plant... in kerala..

2092


difference between power surge and switching transient

2063


why the arc welding machines require parallel earthing systems? ie why each machines are connected to earth pit by separate wires during earthing? wats it adavantages?

2183


In ups static switch if i gives the supply at output end it will open the circuit in stactic switch or not if it will open then how it operates.

2281


How to calibrate or test an LT Air Circuit breaker 440 volts, 35 KA, 800 Amps ?

2585


why we used dc supply for field in dg set

2366


How the annunciator works ? How to do its wiring

2284


what is the formula of starting current of 3phase and 1 phase motor???

2310


How delta connection in the primary of distribution transformer reduces harmonics?how delta connections reduces harmonics?Please answer me...Hope that question is correct.

2193


How maesure earth neutral value & how much maximum value value required in between earth & neutral.

2051


What is transient Phenomenon?

2229


how many current required for hypo test

1956


How out of step protection relay works?

2409