What the capacitor Current formula?, For 1 KVAr how amps
its required? for using the KVAr for boosting the PF Design
Calculation.( Eg: for 30 KVAr required how many KW?)
Answer Posted / kalanidhi
Current calculation for 200 kvar capacitor
CAPACITOR VOLTAGE CALCULATION
#System Voltage (MV) : 433V (WITH +- 5%)
#Voltage drop across (Maximum) : 433 x -5% = 21.65V
Capacitors working : 411.35 Volts.
CAPACITOR CURRENT CALCULATION
KVAR Calculation at 433 Volts.
KVAR 433 Volt (433)2
= ------------ 200KVAR
(411.35)2
187489
= ----------- 200 KVAR
169208
= 1.1 x 200 KVAR = 221.59
= 221.59 KVAR
Current for 221.56 KVAR at 433 V = 221.59
------------------------ x 1000
433 x 1.732 x 0.6
= 492 Amps.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
hello friends this is krunal here.. i have applied for he officer train in hpcl electrical stream.. any one who have applied before for electrical stream please help me out.. post ur reply to my mail id: krunal_airforce@yahoo.com.. any tips, old questions for paper or any help will do.. plz help me.. your faithfully, Krunal Darji
We have a couple of oil tanks at our plant. One of them does not have a lightning arrester installed. My question is it necessary to install an arrestor on every tank or will this particular one be covered by the arrestor installed on the ajdacent tank, Since all the tanks are close to each other. Basically, I want to know that if these arrestors or protection works in a parituclar area of effect or influence. Thanks
How the PF control while running DG set with load
For R-L or R-C ckt,time constant formula is L/R and RC respectively and its unit is in sec.Pls tell me the derivation
what is formula for calculate thermal overload in new numiricalrelay( not in bimetal relay)?
What is the Diff. btw Manule Pull Station & Manule Abort Station Switches used in FM200 System??
which one is more efficient, torq, power & ecnomy with the same frame size AC motor / DC motor?
can u please mail me the syllabus for GET exam for damodar valley corporation?
in HT service 3ph 4 wire service Y-phase voltage shows zero . whether it is meter fault? or what be the reason ? if y-ph voltage zero ,can current is recorded? reasons for failure?
Where can i get practical knowledge of solar system?
What is the de rating factor of cable? What is the importance of the de rating factor in cable select
why +24 v and -48 v give to BTS? If -48v protect from surge then why we not use -24 v?
how ceiling fan worked?
What is the procedure/activities to be taken to inject the current more than 2000A by using 2000A Loading Transformer?
Operation carried out in thermal power stations?